Troubleshooting
Defrost Flow Chart
2-1ERROR DISPLAY
Timer Opeartion Control
Function Setting
Powerful Operation
Service Instruction
Manual auto switch error
Page 4
Image 4
Page 3
Page 5
Page 4
Image 4
Page 3
Page 5
Contents
INVERTER
SERVICE INSTRUCTION
R410A
WALL MOUNTEDtype
1. DESCRIPTION OF EACH CONTROL OPERATION
2. TROUBLE SHOOTING
CONTENTS
3. APPENDING DATA
Page
WALL MOUNTED type
INVERTER
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
1. COOLING OPERATION
2. HEATING OPERATION
3. DRY OPERATION
4. AUTO CHANGEOVER OPERATION
5. INDOOR FAN CONTROL
1. Fan speed
2. FAN OPERATION
3. COOLING OPERATION
5. HEATING OPERATION
6. COOL AIR PREVENTION CONTROL Heating mode
Fig.6 Cool air prevension control
Normal operation
1. Outdoor Fan Motor
6. OUTDOOR FAN CONTROL
2. Fan Speed
7. LOUVER CONTROL
2. ADJUST THE RIGHT-LEFTLOUVERS
Types of Air flow Direction Setting
1. VERTICAL LOUVER CONTROL
1.OPEARTION FREQUENCY RANGE
8.COMPRESSOR CONTROL
2.OPEARTION FREQUENCY CONTROL AT NORMAL START UP
9. TIMER OPEARTION CONTROL
9-1WIRELESS REMOTE CONTROLLER
2. PROGRAM TIMER
1. OPEARTION FREQUENCY RANGE
In the cooling operation mode
3. SLEEP TIMER
In the heating operation mode
11. FOUR-WAYVALVE EXTENSION SELECT
12. AUTO RESTART
17. POWERFUL OPERATION
14. FORCED COOLING OPERATION TEST OPERATION
15. COMPRESSOR PREHEATING
16. ECONOMY OPERATION
1.CONDITION OF STARTING THE DEFROST OPERATION
18. DEFROST OPERATION CONTROL
2. CONDITION OF THE DEFROST OPERATION COMPLETION
3. Defrost Flow Chart
Normal defrost
Integrating defrost
01-14
19. OFF DEFROST OPEARTION CONTROL
OFF Defrost Flow Chart Heating operation stop
1. OFF DEFROST OPERATION CONDITION
2. OFF DEFROST END CONDITION
20. VARIOUS PROTECTIONS
2.CURRENT RELEASE CONTROL
Heating
Heating
4. COOLING PRESSURE OVERRISE PROTECTION
3.ANTIFREEZING CONTROL Cooling and Dry mode
5.HIGH TEMPERATURE RELEASE CONTROL HEATING MODE
2 . TROUBLE SHOOTING
WALL MOUNTED type
INVERTER
R410A
2-1ERROR DISPLAY
2. TROUBLESHOOTING
2-2TROUBLE SHOOTING WITH ERROR CODE
Trouble shooting 1-1OUTDOOR UNIT Error Method
Indicate or Display Refer to error code table
Check Point 3 : Check the voltage of power supply
Trouble shooting 1-2INDOOR UNIT Error Method
Indicate or Display Refer to error code table
Check Point 3 Check the voltage of power supply
Detective Actuators
Trouble shooting 2 INDOOR UNIT Error Method
Indoor unit PCB model information error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 3 INDOOR UNIT Error Method
Manual auto switch error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 4 INDOOR UNIT Error Method
Room temp. sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 5 INDOOR UNIT Error Method
Indoor unit Heat Ex. middle temp. sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 6 INDOOR UNIT Error Method
Indoor unit fan motor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 7 OUTDOOR UNIT Error Method
Indicate or Display Refer to error code table
Check Point 1-1 Reset Power supply and operate
Detective Actuators
Trouble shooting 8 OUTDOOR UNIT Error Method
PFC circuit error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 9 OUTDOOR UNIT Error Method
Trip terminal L error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 10 OUTDOOR UNIT Error Method
Discharge temp. sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 11 OUTDOOR UNIT Error Method
Outdoor unit Heat Ex. liquid temp. sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 12 OUTDOOR UNIT Error Method
Outdoor temp. sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 13 OUTDOOR UNIT Error Method
Current sensor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 14 OUTDOOR UNIT Error Method
Indicate or Display Refer to error code table
Trip detection
Detective Actuators
Trouble shooting 15 OUTDOOR UNIT Error Method
Compressor rotor position detection error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 16 OUTDOOR UNIT Error Method
Outdoor unit fan motor error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 17 INDOOR UNIT Error Method
4-wayvalve error
Indicate or Display Refer to error code table
Detective Actuators
Trouble shooting 18 OUTDOOR UNIT Error Method
Indicate or Display Refer to error code table
Discharge temperature error
Detective Actuators
Indoor Unit - No Power
2-3TROUBLE SHOOTING WITH NO ERROR CODE
Trouble shooting
Outdoor Unit - No Power
Trouble shooting
Power supply failure 2. External cause
Check Point 1 Check Installation Condition
Trouble shooting
No Operation Power is ON
Setting/ Connection failure 2. External cause
Forecast of Cause
Trouble shooting
No Cooling / No Heating
Trouble shooting
1.Abnormal installation Indoor/ Outdoor
Diagnosis method when abnormal noise is occurred
Trouble shooting
SERVICE PARTS INFORMATION
2-4SERVICE PARTS INFORMATION
Compressor
SERVICE PARTS INFORMATION
Inverter Compressor
SERVICE PARTS INFORMATION
If Resistance value is abnormal, replace EEV
If it does not appear, replace Main PCB
CLOSE Example Hot Gas
SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION
Indoor unit fan motor
Outdoor unit fan motor
Page
3 . APPENDING DATA
WALL MOUNTED type
INVERTER
R410A
3-1.FUNCTION SETTING
3-1-1INDOOR UNIT
1-1.Setting the Filter Sign
1-2.Cooling Room Temperature Correction
1-4.Setting the Auto Restart
1-5.Remote controller signal code
STEP Setting the Remote controller Signal Code
Entering the Function Setting Mode
PREPARATION
Selecting the Function Number and Setting Value
STEP
Setting Value
Function
REMOTE CONTROLLER SIGNAL CODE SETTING
3-2-1INDOOR UNIT
3-2.Thermistor Resistance Values
3-2-2OUTDOOR UNIT
Page