Trouble shooting 2 INDOOR UNIT Error Method:

Indoor unit PCB model information error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Indoor unit Controller PCB

Detective details:

When power is on and there is some below case.

1.When model information of EEPROM is incorrect.

2.When the access to EEPROM failed.

Forecast of Cause:

1. External cause 2. Defective connection of electric components 3. Controller PCB failure

Check Point 1-1 : Reset Power Supply and operate

Does Error indication show again?

YES

Check Point 2 :

Check Indoor unit electric components

Check all connectors.

(loose connector or incorrect wiring) Check any shortage or corrosion on PCB.

NO

Check Point 1-2 :

Check external cause such as noise

Check if the ground connection is proper.

Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).

Check Point 3 : Replace Controller PCB

Change Controller PCB.

Note : EEPROM

EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non- volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically.

To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.)

There is a limit in a number of rewriting.

02-04

Page 27