Fujitsu ASU12RL2, AOU12RL2 Trouble shooting 11 OUTDOOR UNIT Error Method, Detective Actuators

Models: ASU12RL2 AOU09RL2 AOU12RL2

1 62
Download 62 pages 59.61 Kb
Page 36
Image 36
Trouble shooting 11 OUTDOOR UNIT Error Method:

Trouble shooting 11 OUTDOOR UNIT Error Method:

Outdoor unit Heat Ex. liquid temp. sensor error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB

Heat exchanger temperature thermistor

Detective details:

When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.

Forecast of Cause :

1. Connector connection failure 2.Thermistor failure 3. Main PCB failure

Check Point 1 : Check connection of Connector

Outdoor unit Heat Ex. liquid temp. sensor error Check if connector is removed.

Manual background Check erroneous connection.

Manual background Check if thermistor cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

Manual background OK

Check Pointi t 2 :: Remove connector and check Thermistor resistance value

Thermistor Characteristics (Approx. value)

Temperature

 

-10°C

-5°C

0°C

5°C

10°C

20°C

30°C

 

(14°F)

(23°F)

(32°F)

(41°F)

(50°F)

(68°F)

(86°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance Value (k

)

27.21

20.80

 

16.05

 

12.47

9.775

6.129

3.947

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

40°C

50°C

 

60°C

 

70°C

80°C

 

 

 

(104°F)

(122°F)

(140°F)

(158°F)

(176°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance Value (k

)

2.606

1.759

 

1.213

 

0.8531

0.6115

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual background If Thermistor is either open or shorted, replace it and reset the power.

Manual background OK

Check Poiintt 3 :: Check voltage of Main PCB (DC5.0V)

Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)

THERMISTOR

 

(PIPE)

BLACK

 

 

BLACK

 

BLACK

THERMISTOR

BLACK

 

(DISCHARGE)

 

THERMISTOR

(OUTDOOR)

BLACK

BLACK

11

22 CN71

33

44

11

22 CN70

33

Manual background If the voltage does not appear, replace Main PCB.

02-13

Page 36
Image 36
Fujitsu ASU12RL2, AOU12RL2 Trouble shooting 11 OUTDOOR UNIT Error Method, Outdoor unit Heat Ex. liquid temp. sensor error