Trouble shooting 22

No Cooling / No Heating

Forecast of Cause:

1.

Indoor Unit error 2. Outdoor unit error

3.

Effect by surrounding environment

4.

Connection pipe / Connection wire failure 5. Refrigeration cycle failure

Check Point 1 : Check Indoor unit

Does Indoor unit Fan run on High fan?

Is Air filter dirty?

Is Heat exchanger clogged?

Check if Energy save function is operated.

OK

Check Point 2 : Check Outdoor unit operation

Check if Outdoor unit is operating

Check any objects that obstruct the air flow route.

Check clogged Heat Exchanger.

Is the Valve open?

OK

Check Point 3 : Check Site condition

Is capacity of Indoor unit fitted to room size?

Any windows open? or direct sunlight ?

OK

Check Point 4 :

Check Indoor/ Outdoor installation condition

Check connection pipe

(specified pipe length & Pipe diameter?)

Check any loose or removed communication line.

>>If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.

OK

MPa MPa

Check Point 5 : Check Refrigeration cycle

Check if Strainer is clogged (Refer to the figure at right). Measure Gas pressure and if there is a leakage, correct it.

>>When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.

Check Capillary tube (PARTS INFORMATION 3)

Check Compressor (PARTS INFORMATION 1,2)

Attention

Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.

Pipe (In)

Pipe (Out)

Pipe (In)

Pipe (Out)

02-24

Page 47
Image 47
Fujitsu AOU09RL2 No Cooling / No Heating, Check Point 2 Check Outdoor unit operation, Check Point 3 Check Site condition