Fujitsu AOU12RL2, ASU12RL2 Trouble shooting 15 OUTDOOR UNIT Error Method, Detective Actuators

Models: ASU12RL2 AOU09RL2 AOU12RL2

1 62
Download 62 pages 59.61 Kb
Page 40
Image 40
Trouble shooting 15 OUTDOOR UNIT Error Method:

Trouble shooting 15 OUTDOOR UNIT Error Method:

Compressor rotor position detection error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB Compressor

Detective details:

Compressor rotor position detection errorIf the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops.

After the compressor restarts, if the same operation is repeated Check Point 3: Replace Main PCB within 40sec, the compressor stops again.

Check Point 4: Replace Compressor If Manual background and Manual background repeats 5 times, the compressor stops permanently.

Forecast of Cause :

1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure

Check Point 1 : Check Noise from Compressor

Turn on Power and check operation noise.

If an abnormal noise show, replace Compressor.

OK

Check Point 2 : Check connection of around the Compressor components

For Compressor Terminal, Main PCB

Manual background Check if connector is removed.

Manual background Check erroneous connection.

Manual background Check if cable is open.

(Refer to PARTS INFORMATION 2)

>>Upon correcting the removed connector or mis-wiring, reset the power.

Manual background OK

Check Point 3: Replace Main PCB

If Check Point 1,2 do not improve the symptom, change Main PCB.

OK

Check Point 4: Replace Compressor

If Check Point 3 do not improve the symptom, change Compressor.

02-17

Page 40
Image 40
Fujitsu AOU12RL2, ASU12RL2 manual Trouble shooting 15 OUTDOOR UNIT Error Method, Compressor rotor position detection error