2. HEATING OPERATION

2. HEATING OPERATION

A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.

*If the room temperature is lower by 3°C (6°F) than a set temperature, the compressor operation frequency will attain to maximum performance.

*If the room temperature is some degrees higher than a set temperature,

the compressor will be stopped.

*When the room temperature is between +2.5°C (+5°F) to -3°C (-6°F) of the setting temperature, the compressor frequency is controlled within the range shown in Table 3.

However, the maximum frequency is limited shown in Table 4 based on the fan mode.

( Table 3 : Compressor frequency range )

 

Minimum

Maximum

 

frequency

frequency

 

 

 

AOU09RL2

18rps

80rps

AOU12RL2

120rps

 

( Table 4 : Limit of maximum speed based on outdoor temperature )

 

 

Indoor fan mode

 

 

 

 

 

 

 

 

 

 

 

 

Hi

Me

Lo

Quiet

Auto

AOU09RL2

 

 

80rps

 

 

AOU12RL2

 

 

120rps

 

 

3. DRY OPERATION

The compressor frequency shall change according to the temperature, set temperature,

and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 5.

However, after the compressor is driven, the indoor unit shall run at operation frequency of (09 : 52 rps, 12 : 61 rps) for 60 seconds.

( Table 5 : Compressor frequency in Dry mode)

 

 

Operating

 

 

frequency

AO09RL2

X zone

30rps

 

J zone

28rps

 

Y zone

0rps

 

 

Operating

 

 

frequency

AO12RL2

X zone

33rps

 

J zone

25rps

 

Y zone

0rps

( Fig.2 : Compressor control based on room temperature )

 

 

When the room

When the room

temperature rises

temperature drops

 

Ts+1.5°C (Ts+3°F)

 

 

 

 

Ts+0.5°C (Ts+1°F)

X zone

 

 

 

 

Ts -0.5°C (Ts-1°F)

 

 

 

Ts -1.5°C (Ts-3°F)

J zone

 

 

 

 

 

 

Y zone

 

 

 

 

 

 

 

 

 

01-02