Trouble shooting 13 OUTDOOR UNIT Error Method:

Trouble shooting 13 OUTDOOR UNIT Error Method:

Current sensor error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Outdoor unit Main PCB

Detective details:

When Input Current Sensor has detected 0A, while Inverter Compressor is operating at higher than 56rps, after 1minute upon starting the Compressor. (Except during the defrost operation)

Forecast of Cause :

 

 

1. Defective connection of electric components

2. External cause

3. Main PCB failure

Check Point 1-1 : Reset Power Supply and operate

Current sensor error Does Error indication show again?

YES

NO

Check Point 2 :

Check connections of Outdoor Unit Electrical Components

Manual background Check if the terminal connection is loose.

Manual backgroundCheck if connector is removed.

Manual backgroundCheck erroneous connection.

Manual backgroundCheck if cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

OK

Check Point 1-2 :

Check external cause at Indoor and Outdoor (Voltage drop or Noise)

Manual background Instant drop : Check if there is a large load electric apparatus in the same circuit.

Manual background Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.

Manual background Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.

Check Point 4 : Replace Main PCB

Manual background If Check Point 1, 2 do not improve the symptom, change Main PCB.