Trouble shooting 4 INDOOR UNIT Error Method:

Room temp. sensor error

Indicate or Display:

Refer to error code table.

Detective Actuators:

Indoor unit Controller PCB Room temperature thermistor

Detective details:

When Room temperature thermistor open or short-circuit is detected.

Forecast of Cause :

1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure

Check Point 1 : Check connection of Connector

Check if connector is removed.

Check erroneous connection.

Check if thermistor cable is open.

>>Upon correcting the removed connector or mis-wiring, reset the power.

OK

 

 

 

 

 

 

 

 

 

Check Point 2 : Remove connector and check Thermistor resistance value

 

 

Thermistor Characteristics (Approx. value)

 

 

 

 

 

 

Temperature

 

-10°C

-5°C

0°C

5°C

10°C

15°C

20°C

25°C

 

(14°F)

(23°F)

(32°F)

(41°F)

(50°F)

(59°F)

(68°F)

(77°F)

 

 

Resistance Value (k

)

55.46

42.36

32.67

25.39

19.91

15.71

12.5

10.0

Temperature

 

30°C

35°C

40°C

45°C

 

 

 

 

 

(86°F)

(95°F)

(104°F)

(113°F)

 

 

 

 

 

 

 

 

 

 

Resistance Value (k

)

8.051

6.52

5.316

4.354

 

 

 

 

If Thermistor is either open or shorted, replace it and reset the power.

 

 

 

OK

 

 

 

 

 

 

 

 

 

Check Point 3 : Check voltage of Controller PCB (DC5.0V)

Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)

THERMISTOR

 

 

 

(PIPE)

 

 

 

BLACK

1

1

 

BLACK

2

2

CN4

BLACK

3

3

 

BLACK

4

4

 

THERMISTOR

 

 

 

(ROOM TEMP.)

 

 

 

If the voltage does not appear, replace Controller PCB.

02-06

Page 29
Image 29
Fujitsu AOU09RL2, ASU12RL2, AOU12RL2 manual Indoor unit Controller PCB Room temperature thermistor