Trouble shooting 18 OUTDOOR UNIT Error Method:
Discharge temperature error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Discharge temperature thermistor
Detective details:
"Protection stop by "discharge temperature  110degC during compressor operation"" generated 2 times within 24 hours.
 110degC during compressor operation"" generated 2 times within 24 hours.
| Forecast of Cause : 1. | 2/  | 2. Capillary tube, strainer clogged | 
| 3. | Outdoor unit operation failure, foreign matter on heat exchanger | |
| 4. | Discharge temperature thermistor failure | 5. Insufficient refrigerant | 
| 6. | Main PCB failure | 
 | 
| 
 | 
 | 
 | 
<Cooling operation>
Check Point 1 : Check if 
 If the
 If the 
<Heating operation>
Check Point 1 : Check if 
 If the
 If the 
OK
Check Point 2 : Check the capillary tube, strainer
 Capillary tube, Strainer(after Capillary) clogging check. Refer to "Service Parts Information 3".
 Capillary tube, Strainer(after Capillary) clogging check. Refer to "Service Parts Information 3".
OK
Check Point 2 : Check the capillary tube, strainer
 Capillary tube, Strainer(before Capillary) clogging check. Refer to "Service Parts Information 3".
 Capillary tube, Strainer(before Capillary) clogging check. Refer to "Service Parts Information 3".
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
 Check for foreign object at heat exchanger
 Check for foreign object at heat exchanger
 Check if fan can be rotated by hand.
 Check if fan can be rotated by hand.
 Motor check (PARTS INFORMATION 5)
 Motor check (PARTS INFORMATION 5)
OK
Check Point 4 : Check the discharge thermistor
 Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
 Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
OK
* For the characteristics of the thermistor, refer to the "Trouble shooting 10".
OK
Check Point 5 : Check the refrigerant amount
 Leak check
 Leak check