SERVICE PARTS INFORMATION 3

Outdoor unit Electronic Expansion Valve ( EEV )

Check Point 1 : Check Connections

Check connection of connector (CN40) ( Loose connector or open cable )

 

 

 

EXPANSION

 

1 1

RED

VALVE COIL

 

2 2

BLUE

EV

CN40

3 3

YELLOWORANGE

 

4 4

WHITE

 

 

5 5

 

Check Point 2 : Check Coil of EEV

Remove connector, check each winding resistance of Coil.

Read wire

Resistance value

White - Red

 

 

 

 

 

Yellow - Red

46

4

 

 

 

 

 

 

Orange - Red

at 20°C

 

 

 

Blue - Red

 

 

 

 

 

 

 

 

 

 

 

If Resistance value is abnormal, replace EEV.

Check Point 3 : Check Voltage from Main PCB.

DC

Remove Connector and check Voltage (DC12V)

If it does not appear, replace Main PCB.

 

Check Point 4 : Check Noise at start up

Turn on Power and check operation noise.

If an abnormal noise does not show, replace Main PCB.

Check Point 5 : Check Opening and Closing Operation of Valve

When Valve is closed,

it has a temp. difference between Inlet and Outlet.

If it is open,

it has no temp. difference between Inlet and Outlet.

CLOSE

Example : Hot Gas

Pipe (In)

Hi TEMP.

Pipe (Out)

Normal TEMP.

OPEN Example : Hot Gas

Pipe (In)

Hi TEMP.

Pipe (Out)

Hi TEMP.

Check Point 6 : Check Strainer

Strainer normally does not have temperature difference between inlet and outlet as shown in ,

but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.

Pipe (In)

Pipe (Out)

Pipe (In)

Pipe (Out)

 

 