Fujitsu AOU12RL2, ASU12RL2, AOU09RL2 Trouble shooting, No Operation Power is ON, Forecast of Cause

Models: ASU12RL2 AOU09RL2 AOU12RL2

1 62
Download 62 pages 59.61 Kb
Page 46
Image 46
No Operation (Power is ON)

Trouble shooting 21

No Operation (Power is ON)

Forecast of Cause:

1.

Setting/ Connection failure 2. External cause

3.

Electrical component defective

Check Point 1 : Check indoor and outdoor installation condition

Setting/ Connection failure 2. External cause Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?

>>If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.

Electrical component defective OK

Turn off Power and check/ correct followings.

Manual background Is there loose or removed communication line of Indoor Unit and Outdoor Unit?

OK

Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)

Instant drop -----

Check if there is a large load electric apparatus in the same circuit.

Momentary power failure -----

Check if there is a defective contact or leak current in the power supply circuit.

Noise -----

Check if there is any equipment causing harmonic wave near electric line.

 

(Neon bulb or electric equipment that may cause harmonic wave)

 

Check the complete insulation of grounding.

Manual background OK

Manual background If the symptom does not change by above Check 1, 2, replace Main PCB.

02-23

Page 46
Image 46
Fujitsu AOU12RL2, ASU12RL2 Trouble shooting, No Operation Power is ON, Forecast of Cause, Electrical component defective