19. OFF DEFROST OPEARTION CONTROL

19. OFF DEFROST OPEARTION CONTROL

When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit Operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.

1. OFF DEFROST OPERATION CONDITION

In heating operation, the outdoor heat exchanger temperature is less than - 4°C (24.8°F), compressor continuous operation more than 10 minutes, and

compressor operation integrating time lasts for more than 30 minutes.

2. OFF DEFROST END CONDITION

Release Condition

Outdoor heat exchanger temperature sensor value is higher than 16°C (60.8°F) or Compressor operation time has passed 15 minutes.

OFF Defrost Flow Chart

Heating operation stop

1. OFF DEFROST OPERATION CONDITION Outdoor heat exchanger temperature :

Below - 4°C (24.8°F)

2. OFF DEFROST END CONDITION Compressor continuous operation :

Over 10 minutes

OFF Defrost Flow Chart Compressor integrating operation :

Over 30 minutes

Defrost start

Defrost Indicater: [Operation lamp]

7 sec ON / 2 sec OFF

Outdoor heat exchanger temperature:

Over 16°C (60.8°F) or

Compressor ON time: Over 15 minutes

Defrost end