50.(00110010) Phase 2 to 5 - Hot Valve Fault

The Motor Controller has measured a voltage from the valve diagnostic circuit that indicates that the hot valve is faulty. The most likely cause is that the valve harness has not been connected correctly.

Primary Source - Wiring

Action - Check valve harnesses are correctly fastened to valves.

Secondary Source - Water Valves

Action - Check valve coils are not faulty ( open circuit ). If either of these valves are low impedance it is likely that the Motor Control output has also failed, in which case replace Motor Controller and valve(s).

NB. Phase 5 can give fault code 50 when Smartdrive powers off while spinning. In this case there will be no fault.

51.(00110011) Phase 5 ECO – Recirculation Fault

The product has detected that it is losing water during recirculation.

Primary Source – Diverter Valve Wiring

Action - Check diverter valve harness is correctly fastened to diverter valve. Check flying lead in motor controller, and connection to valve next to drain pump.

Secondary Source – Diverter Valve

Action - Check diverter valve resistance. If open circuit (nominal is 1500 ohms) replace diverter valve. During recirculation, check that water is being recirculated back into the bowl, and that no water is coming out of drain hose. If there is some water coming from the drain hose, then the diverter valve could be faulty, or it could be jammed with a foreign object. Replace diverter valve.

Tertiary Source - Motor Controller

Action - The diverter valve drive circuit may be at fault. If the primary and secondary checks pass inspection then replace the Motor Controller.

52.(00110100) Phase 5 ECO – Recirculation Fault See fault code 51.

- 52 -

Page 57
Image 57
Fisher & Paykel 517735 Phase 2 to 5 Hot Valve Fault, Phase 5 ECO Recirculation Fault, Secondary Source Diverter Valve