Bryant 581A/B ARI* Capacity Ratings 579F180-300, Heating Capacities and Efficiencies 579F180-300

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 12
Image 12

ARI* CAPACITY RATINGS — 579F180-300

LOW HEAT UNITS

UNIT

NOMINAL

NET COOLING

 

TOTAL

 

SOUND

 

CAPACITY

 

EER

RATING

IPLV

579F

TONS

 

WATTS

(Btuh)

 

 

(dB)

 

 

 

 

 

 

 

180

15

174,000

20,128

8.6

88

9.3

216

18

188,000

21,619

8.7

88

9.5

240

20

220,000

25,513

8.6

94

8.7

300

25

268,000

31,068

8.6

94

9.2

 

 

HIGH HEAT UNITS

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOMINAL

NET COOLING

 

TOTAL

 

SOUND

 

CAPACITY

 

EER

RATING

IPLV

579F

TONS

 

WATTS

(Btuh)

 

 

(dB)

 

 

 

 

 

 

 

180

15

174,000

 

20,154

8.6

88

9.3

216

18

186,000

 

21,798

8.5

88

9.3

240

20

218,000

 

25,719

8.5

94

8.5

300

25

268,000

 

31,600

8.5

94

8.9

 

LEGEND

 

 

 

 

 

 

dB

Sound Levels (decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio

IPLV

Integrated Part-Load Values

wb

Wet Bulb

*Air Conditioning and Refrigeration Institute.

NOTES:

1.Rated in accordance with ARI Standards 360 and 270.

2.The 579F300 is beyond the scope of the ARI Certification Program.

3.ARI ratings are net values, reflecting the effects of circulating fan heat.

4.Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db air entering outdoor unit.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

HEATING CAPACITIES AND EFFICIENCIES — 579F180-300

UNIT

HEATING INPUT

OUTPUT CAPACITY

TEMPERATURE

STEADY-STATE

MINIMUM

(Btuh)

579F

(Btuh)

RISE (F)

EFFICIENCY (%)

HEATING CFM

Stage 2/Stage 1*

 

 

 

 

 

180230

230,000/172,000

186,000

15-45

81.0

3830

180300

300,000/225,000

243,000

30-60

81.0

3750

216275

275,000/206,000

223,000

15-45

81.0

4580

216360

360,000/270,000

292,000

20-50

81.0

5400

240275

275,000/206,000

223,000

15-45

81.0

4580

240360

360,000/270,000

292,000

20-50

81.0

5400

300275

275,000/206,000

223,000

15-45

81.0

4580

300360

360,000/270,000

292,000

20-50

81.0

5400

*All units are 2-stage heat.

NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating. For entering-air temperatures below 45 F both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation.

AIR QUANTITY LIMITS

UNIT 579F

MINIMUM CFM

MAXIMUM CFM

180

4500

7,500

216

5400

9,000

240

6000

10,000

300

7000

11,250

LOW OUTDOOR TEMPERATURE

OPERATING LIMITS (F)

UNITS

TEMPERATURE

All

40

180 and 216 with Low Ambient Kit

10

240 and 300 with Low Ambient Kit

25

All with Motormaster® Head Pressure Control

–20

12

Page 12
Image 12