Bryant 581A/B manual Physical Data 580F180-300, Txv

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 172
Image 172

PHYSICAL DATA — 580F180-300

 

 

 

 

UNIT 580F

 

 

180

 

210

 

240

 

300

 

 

 

NOMINAL CAPACITY (tons)

 

 

15

 

18

 

20

 

25

 

 

 

OPERATING WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

1800

1850

 

1900

 

2270

 

 

 

EconoMi$er IV

 

 

80

 

80

 

80

 

80

 

 

 

COMPRESSOR/MANUFACTURER

 

 

 

 

Scroll, Copeland

 

 

 

 

 

Quantity...Model (Ckt 1, Ckt 2)

 

1...ZR94KC,

1...ZR108KC,

 

1...ZR125KC,

 

1...ZR4140KC,

 

 

 

Capacity Stages (%)

 

1...ZR72KC

1...ZR94KC

 

1...ZR108KC

 

2...ZR144KC

 

 

 

 

60, 40

55, 45

 

55, 45

 

60, 40

 

 

 

Number of Refrigerant Circuits

 

 

2

 

2

 

2

 

2

 

 

 

Oil (oz) (Ckt 1, Ckt 2)

 

85, 60

106, 81

 

106,106

 

136, 106

 

 

 

REFRIGERANT TYPE

 

 

 

 

 

 

R-22

 

 

 

 

 

Expansion Device

 

 

 

 

 

 

TXV

 

 

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1*

 

 

19-8

 

19-8

 

19-11

 

26-13

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 2

 

 

13-8

 

19-2

 

13-14

 

25-10

 

 

 

CONDENSER COIL

 

 

Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced,

 

 

 

 

 

 

 

 

Aluminum Pre-Coated, or Copper Plate Fins

 

 

 

Rows...Fins/in.

 

4...15

4...15

 

4...15

 

3...15 (2 coils)

 

 

 

Total Face Area (sq ft)

 

 

21.7

 

21.7

 

21.7

 

43.4

 

 

 

CONDENSER FAN

 

 

 

 

Propeller Type

 

 

 

 

 

Nominal Cfm

 

10,500

10,500

 

14,200

 

21,000

 

 

 

Quantity...Diameter (in.)

 

3...22

3...22

 

2...30

 

6...22

 

 

 

Motor Hp...Rpm

 

1/

...1050

1/

...1050

 

1...1075

 

1/ ...1050

 

 

 

Watts Input (Total)

 

2

 

2

 

 

3400

 

2

 

 

 

 

1100

1100

 

 

2200

 

 

 

EVAPORATOR COIL

 

 

Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced or

 

 

 

 

 

 

 

 

 

Copper Plate Fins, Face Split

 

 

 

 

 

Rows...Fins/in.

 

4...15

4...15

 

4...15

 

4...15

 

 

 

Total Face Area (sq ft)

 

 

17.5

 

17.5

 

17.5

 

17.5

 

 

 

EVAPORATOR FAN

 

 

 

 

Centrifugal Type

 

 

 

 

 

Quantity...Size (in.)

 

2...12 x 12

2...12 x 12

 

2...12 x 12

 

2...12 x 12

 

 

 

Type Drive

 

 

Belt

 

Belt

 

Belt

 

Belt

 

 

 

Nominal Cfm

 

6000

7200

 

8000

 

10,000

 

 

 

Motor Hp

 

 

5

 

5

 

7.5

 

10

 

 

 

Motor Nominal Rpm

 

1745

1745

 

1745

 

1740

 

 

 

Maximum Continuous Bhp

 

 

6.13

 

5.90

 

8.7 [208/230, 575 v]

 

10.2 [208/230, 575 v]

 

 

 

 

 

 

 

9.5 [460 v]

 

11.8 [460 v]

 

 

 

Motor Frame Size

 

 

 

 

 

 

 

 

 

 

 

184T

184T

 

213T

 

215T

 

 

 

Nominal Rpm High/Low

 

 

 

 

 

 

 

 

Fan Rpm Range

Low-Medium Static

873-1021

910-1095

 

1002-1151

 

1066-1283

 

 

 

Motor Bearing Type

High Static

1025-1200

1069-1287

 

1193-1369

 

1332-1550

 

 

 

 

 

Ball

 

Ball

 

Ball

 

Ball

 

 

 

Maximum Allowable Rpm

 

1550

1550

 

1550

 

1550

 

 

 

Motor Pulley Pitch Diameter

Low-Medium Static

4.9/5.9

4.9/5.9

 

5.4/6.6

 

4.9/5.9

 

 

 

 

Min/Max (in.)

High Static

4.9/5.9

4.9/5.9

 

5.4/6.6

 

4.9/5.9

 

 

 

Nominal Motor Shaft Diameter (in.)

Low-Medium Static

 

11/8

 

11/8

 

13/8

 

13/8

 

 

 

Fan Pulley Pitch Diameter (in.)

 

9.4

 

9.4

 

9.4

 

8.0

 

 

 

Nominal Fan Shaft Diameter (in.)

High Static

 

8.0

 

8.0

 

7.9

 

6.4

 

 

 

Low-Medium Static

 

17/16

 

17/16

 

17/16

 

17/16

 

 

 

Belt, Quantity...Type...Length (in.)

1...BX...50

1...BX...50

 

1...BX...53

 

2...BX...50

 

-300

 

Pulley Center Line Distance (in.)

High Static

1...BX...48

1...BX...48

 

1...BX...50

 

2...BX...47

 

 

 

13.3-14.8

13.3-14.8

 

14.6-15.4

 

14.6-15.4

 

 

Speed Change per Full Turn of

Low-Medium Static

 

37

 

37

 

37

 

36

 

580F180

 

Factory Speed Setting (rpm)

Low-Medium Static

 

965

1002

 

1095

 

1182

 

 

 

 

Movable Pulley Flange (rpm)

High Static

 

44

 

34

 

44

 

45

 

 

 

Movable Pulley Maximum Full Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

From Closed Position

 

 

4

 

6

 

6

 

6

 

 

 

Factory Speed

 

 

3.5

 

3.5

 

3.5

 

3.5

 

 

 

Fan Shaft Diameter at Pulley (in.)

High Static

1134

1178

 

1303

 

1470

 

 

 

 

 

17/16

 

17/16

 

17/16

 

17/16

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

Bhp

Brake Horsepower

 

 

 

 

 

 

 

 

 

 

 

 

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

 

 

 

*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils.

†Rollout switch is manual reset.

**The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).

NOTE: The 580F180-300 units have a low-pressure switch (standard) located on the suction side.

172

Page 172
Image 172
Bryant 581A/B manual Physical Data 580F180-300, Txv

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.