PERFORMANCE DATA (cont)

COOLING CAPACITIES, STANDARD UNITS (cont)

 

 

 

581B120 (10 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

Air Ent

 

 

3000/0.03

 

 

3200/0.03

 

 

4000/0.04

 

 

5000/0.04

 

 

 

 

Condenser

 

 

 

 

 

Air Entering Evaporator — Ewb

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

72

67

62

72

67

62

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

140.3

129.4

115.0

141.2

130.4

118.1

145.2

134.0

122.1

147.5

136.6

125.3

 

 

 

75

 

SHC

 

65.6

82.2

97.4

66.7

84.4

101.5

71.3

93.1

113.5

77.9

103.7

124.7

 

 

 

 

 

kW

 

7.35

7.21

7.12

7.37

7.23

7.13

7.46

7.31

7.17

7.51

7.37

7.22

 

 

 

 

 

TC

 

137.7

125.3

110.0

138.9

126.6

113.6

142.6

130.6

117.7

144.6

133.3

122.3

 

 

 

85

 

SHC

 

65.0

81.2

95.2

66.3

83.6

99.7

71.0

92.8

112.0

76.9

103.1

122.2

 

 

 

 

 

kW

 

8.29

8.13

8.02

8.32

8.16

8.03

8.40

8.24

8.09

8.45

8.31

8.16

 

 

 

95

 

TC

 

133.8

120.7

103.0

135.1

121.9

107.2

138.8

125.8

112.8

141.7

128.5

118.5

 

 

 

 

SHC

 

63.9

79.6

92.2

65.2

82.0

97.0

70.6

91.5

109.7

76.9

102.5

118.4

 

 

 

 

 

kW

 

9.33

9.16

8.98

9.35

9.18

9.00

9.44

9.27

9.07

9.51

9.33

9.19

 

 

 

 

 

TC

 

128.7

115.4

96.5

129.8

116.6

99.7

133.7

120.3

107.1

136.7

122.8

114.5

 

150

 

105

 

SHC

 

62.3

77.6

89.4

63.6

80.2

93.5

69.4

89.6

106.8

76.0

100.6

114.3

 

 

 

 

kW

 

10.46

10.28

10.00

10.47

10.30

10.07

10.57

10.38

10.21

10.66

10.43

10.31

 

 

 

 

TC

 

123.2

109.1

90.8

124.3

110.3

92.2

127.9

114.4

100.8

130.9

116.8

110.1

 

581B036-

 

115

 

SHC

 

60.4

75.1

86.6

61.9

77.8

90.0

67.6

87.6

100.7

74.6

98.7

109.9

 

 

 

 

kW

 

11.66

11.47

11.20

11.68

11.51

11.25

11.77

11.60

11.41

11.89

11.66

11.58

 

 

 

 

 

 

 

 

 

 

 

TC

 

117.5

101.8

86.2

118.5

103.0

87.4

121.6

107.1

96.0

124.1

110.3

104.8

 

 

 

125

 

SHC

 

58.5

72.5

84.5

60.0

75.0

87.3

65.8

85.1

96.0

72.5

96.9

104.8

 

 

 

 

 

kW

 

12.99

12.77

12.50

13.02

12.81

12.55

13.10

12.92

12.74

13.19

13.01

12.91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B150 (121/

TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

Air Ent

 

 

3750/0.08

 

 

4300/0.09

 

 

5000/0.11

 

 

6250/0.13

 

 

 

 

Condenser

 

 

 

 

 

Air Entering Evaporator — Ewb

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

72

67

62

72

67

62

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

167.1

154.3

142.0

169.8

157.7

144.8

173.5

160.6

148.4

176.5

164.5

153.3

 

 

 

75

 

SHC

 

82.5

103.5

123.6

85.8

109.7

132.0

90.3

117.7

141.9

98.2

130.7

153.1

 

 

 

 

 

kW

 

9.44

9.18

8.95

9.50

9.26

9.01

9.60

9.33

9.07

9.68

9.43

9.17

 

 

 

 

 

TC

 

162.3

149.3

135.6

165.1

152.5

139.5

168.8

155.3

143.5

172.1

159.2

149.3

 

 

 

85

 

SHC

 

80.9

101.4

120.9

84.4

107.9

129.9

89.6

115.8

139.8

97.6

129.3

149.1

 

 

 

 

 

kW

 

10.49

10.18

9.97

10.55

10.27

10.02

10.67

10.32

10.11

10.75

10.43

10.21

 

 

 

95

 

TC

 

156.5

143.7

126.3

159.6

146.8

131.3

162.3

149.8

136.5

166.5

153.2

144.5

 

 

 

 

SHC

 

79.1

99.5

116.5

83.0

106.1

126.0

87.6

114.2

135.8

95.8

127.7

144.4

 

 

 

 

 

kW

 

11.60

11.30

11.01

11.69

11.39

11.10

11.75

11.47

11.20

11.87

11.56

11.35

 

 

 

 

 

TC

 

150.0

136.2

115.7

153.0

139.3

120.9

155.6

142.5

138.5

158.8

145.9

138.8

 

 

 

105

 

SHC

 

76.5

96.7

111.2

80.8

103.5

120.0

85.7

112.3

128.4

93.6

125.9

138.7

 

 

 

 

 

kW

 

12.76

12.42

12.09

12.83

12.52

12.20

12.91

12.62

12.32

12.96

12.72

12.52

 

 

 

 

 

TC

 

141.8

122.2

104.4

144.3

126.1

110.8

147.7

129.4

118.9

150.7

135.2

130.1

 

 

 

115

 

SHC

 

73.6

91.2

104.2

77.9

98.5

110.8

83.4

107.3

118.4

91.8

121.9

129.9

 

 

 

 

 

kW

 

13.85

13.55

13.22

13.94

13.64

13.35

14.05

13.73

13.50

14.15

13.86

13.70

 

 

 

 

 

TC

 

132.5

108.6

93.9

134.8

111.4

100.7

137.6

114.4

106.6

140.3

122.9

120.1

 

 

 

125

 

SHC

 

70.9

85.7

93.8

74.8

92.9

100.7

80.2

101.4

106.5

89.0

116.3

120.1

 

 

 

 

 

kW

 

15.04

14.66

14.44

15.14

14.75

14.55

15.23

14.85

14.72

15.29

14.94

14.84

 

 

 

Standard Ratings

 

 

 

LEGEND

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb —

Entering Wet Bulb

kW

Compressor Motor Power Input

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

t

 

=

t

sensible capacity (Btuh)

ldb

 

edb

 

1.10 x cfm

 

 

 

 

 

tlwb

= Wet-bulb temperature corresponding to enthalpy of air leaving

 

 

 

evaporator coil (hlwb)

h

lwb

=

h

total capacity (Btuh)

 

 

ewb

 

4.5 x cfm

 

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil.

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).