Bryant 581A/B manual Power Exhaust Electrical Data

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 75
Image 75

ELECTRICAL DATA

UNIT SIZE

 

NOMINAL

 

IFM

 

CONV

VOLTAGE RANGE

COMPRESSOR (each)

 

OFM (each)

IFM

COMBUSTION

 

POWER SUPPLY

 

MINIMUM UNIT

 

 

 

 

FAN MOTOR

 

 

DISCONNECT SIZE*

580F

 

 

V-PH-Hz

 

TYPE

 

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

FLA

 

 

 

 

 

 

 

 

 

 

 

Min

Max

Qty

RLA

LRA

 

Qty

 

FLA

 

FLA

 

MCA

 

MOCP†

 

FLA

 

LRA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

25.2

 

35

 

 

24

 

 

106

 

 

 

208/230-1-60

 

 

YES

187

 

254

 

1

16.2

96

 

1

 

1.4

0.6

 

 

 

31.2

 

35

 

 

30

 

 

111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALT

 

NO

 

 

 

 

4.9

 

 

 

26.6

 

40

 

 

26

 

 

111

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32.6

 

40

 

 

31

 

 

116

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

17.7

 

25

 

 

17

 

 

85

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23.7

 

25

 

 

23

 

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

 

ALT

 

NO

187

 

254

 

1

10.2

75

 

1

 

1.4

4.9

0.6

 

 

 

19.1

 

25

 

 

19

 

 

90

 

 

 

 

 

YES

 

 

 

 

 

 

 

25.1

 

30

 

 

25

 

 

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

5.2

 

 

 

 

 

19.4

 

25

 

 

19

 

 

109

036

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25.4

 

30

 

 

25

 

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3 Ton)

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

1.3

 

 

 

 

 

7.6

 

15

 

 

7

 

 

44

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.3

 

15

 

 

10

 

 

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

 

ALT

 

NO

414

 

508

 

1

4.4

40

 

1

 

0.8

2.1

0.3

 

 

 

8.4

 

15

 

 

8

 

 

48

 

 

 

 

 

YES

 

 

 

 

 

 

 

11.1

 

15

 

 

11

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

2.6

 

 

 

 

 

8.9

 

15

 

 

9

 

 

57

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.6

 

15

 

 

11

 

 

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALT

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

1.9

 

 

 

 

 

7.1

 

15

 

 

7

 

 

37

 

 

 

575-3-60

 

 

YES

518

 

632

 

1

3.7

31

 

1

 

0.6

0.3

 

 

 

9.3

 

15

 

 

9

 

 

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

2.0

 

 

 

7.2

 

15

 

 

8

 

 

44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.4

 

15

 

 

10

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

34.0

 

40

 

 

32

 

 

129

 

 

 

208/230-1-60

 

 

YES

187

 

254

 

1

23.3

118

 

1

 

1.4

0.6

 

 

 

40.0

 

45

 

 

38

 

 

134

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALT

 

NO

 

 

 

 

4.9

 

 

 

35.4

 

45

 

 

34

 

 

133

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.4

 

50

 

 

40

 

 

138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

24.2

 

30

 

 

23

 

 

101

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30.2

 

35

 

 

29

 

 

106

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

 

ALT

 

NO

187

 

254

 

1

15.4

90

 

1

 

1.4

4.9

0.6

 

 

 

25.6

 

30

 

 

25

 

 

105

 

 

 

 

 

YES

 

 

 

 

 

 

 

31.6

 

35

 

 

30

 

 

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

5.2

 

 

 

 

 

25.9

 

30

 

 

25

 

 

124

048

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.9

 

35

 

 

31

 

 

129

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4 Ton)

 

 

 

 

STD

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

 

 

 

 

13.0

 

20

 

 

13

 

 

51

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.7

 

20

 

 

15

 

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

 

ALT

 

NO

414

 

508

 

1

8.3

45

 

1

 

0.8

2.1

0.3

 

 

 

13.3

 

20

 

 

13

 

 

53

 

 

 

 

 

YES

 

 

 

 

 

 

 

16.0

 

20

 

 

15

 

 

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

2.6

 

 

 

 

 

13.8

 

20

 

 

13

 

 

62

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16.5

 

20

 

 

16

 

 

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALT

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

1.9

 

 

 

 

 

10.5

 

15

 

 

10

 

 

42

 

 

 

575-3-60

 

 

YES

518

 

632

 

1

6.4

36

 

1

 

0.6

0.3

 

 

 

12.7

 

15

 

 

12

 

 

43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

 

NO

 

 

 

 

2.0

 

 

 

10.6

 

15

 

 

10

 

 

49

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.8

 

15

 

 

12

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

Determine percent of voltage imbalance.

 

 

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

HACR

Heating, Air Conditioning and Refrigeration

 

 

 

 

 

 

% Voltage Imbalance = 100 x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

457

 

 

 

 

 

 

 

 

 

 

 

 

 

IFM

Indoor (Evaporator) Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= 1.53%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

MOCP — Maximum Overcurrent Protection

 

 

 

 

 

 

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local

NEC

National Electrical Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electric utility company immediately.

 

 

 

 

 

 

 

 

 

 

 

OFM

Outdoor (Condenser) Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

3. For units with power exhaust: If a single power source is to be used, size wire to include

*Used to determine minimum disconnect per NEC.

 

 

 

 

 

 

power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered

 

 

 

 

 

 

through the unit (must be in accordance with NEC and/or local codes). Determine the new

†Fuse or HACR circuit breaker.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA including the power exhaust using the following formula:

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA New = MCA unit only + MCA of Power Exhaust

 

 

 

 

 

 

 

 

1. In compliance with NEC requirements for multimotor and combination load equipment (refer

 

 

 

 

 

 

 

 

 

 

 

 

For

example,

using a

580F060 unit

with MCA

 

= 28.9 and MOCP = 35, with

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or

 

 

 

 

 

CRPWREXH030A01 power exhaust.

 

 

 

 

 

 

 

 

 

 

 

HACR breaker. Canadian units may be fuse or circuit breaker.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Unbalanced 3-Phase Supply Voltage

 

 

 

 

 

 

 

 

 

 

MCA New = 28.9 amps + 1.6 amps = 30.5 amps

 

 

 

 

 

 

 

 

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use

 

 

If the new MCA does not exceed the published MOCP, then MOCP would not change. The

the following formula to determine the percent of voltage imbalance.

 

 

 

 

 

 

 

 

MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is

% Voltage Imbalance

 

 

 

 

 

 

 

 

 

 

 

 

 

acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next

 

 

 

 

max voltage deviation from average voltage

 

 

 

 

 

 

larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

= 100 x

 

 

 

 

 

 

 

 

 

 

 

POWER EXHAUST ELECTRICAL DATA

 

 

 

 

 

average voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example: Supply voltage is 460-3-60.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AB = 452 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOCP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER EXHAUST

APPLICATION

 

MCA

 

 

MCA

 

MCA

 

(separate

 

 

 

 

BC = 464 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PART NO.

USAGE

 

(230 V)

 

(460 V)

 

(575 V)

 

power source

 

 

 

 

AC = 455 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only)

 

 

 

 

Average Voltage =

 

 

452 + 464 + 455

 

 

 

 

 

 

 

 

CRPWREXH030A01

036-073*

 

1.6

 

 

N/A

 

0.64

 

15

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

CRPWREXH021A01

036-073

 

 

N/A

 

0.68

 

 

N/A

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1371

 

 

 

 

 

 

 

 

 

 

CRPWREXH022A01

090-151*

 

3.4

 

 

N/A

 

1.32

 

15

 

 

 

 

 

 

=

 

 

 

 

 

 

 

 

 

 

 

 

CRPWREXH023A01

090-151

 

 

N/A

 

1.4

 

 

N/A

 

15

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRPWREXH028A01

 

ALL*

 

1.7

 

 

N/A

 

0.68

 

15

 

 

 

 

 

 

= 457

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRPWREXH029A01

 

ALL

 

N/A

 

0.7

 

 

N/A

 

15

Determine maximum deviation from average voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(AB) 457 – 452 = 5 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Single or three phase.

 

 

 

 

 

 

 

 

 

 

 

(BC) 464 – 457 = 7 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(AC) 457 – 455 = 2 v

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum deviation is 7 v.

580F036-151

75

Page 75
Image 75
Bryant 581A/B manual Power Exhaust Electrical Data

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.