PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

 

 

 

 

579F216 (18 Tons)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm

 

 

 

 

 

 

 

 

 

Air Entering

 

 

 

 

5400

 

 

 

 

 

 

6000

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

Evaporator Air — Ewb (F)/BF

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54/0.49

58/0.31

62/0.20

67/0.18

72/0.16

76/0.19

80/0.05

54/0.53

58/0.35

62/0.23

67/0.19

72/0.17

76/0.19

80/0.05

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

194

198

206

223

243

260

277

200

203

210

227

246

263

 

 

 

 

75

SHC

 

194

178

169

146

121

99

79

200

191

177

152

125

102

 

 

 

 

 

kW

 

13.6

13.7

13.9

14.2

14.6

15.0

15.2

13.7

13.8

14.0

14.4

14.7

15.1

 

 

 

 

 

TC

 

189

192

200

217

235

252

269

195

195

204

220

239

255

 

 

 

 

85

SHC

 

189

176

166

143

118

97

76

195

195

174

149

123

100

 

 

 

 

 

kW

 

15.1

15.2

15.4

15.9

16.3

16.6

16.9

15.3

15.3

15.7

16.0

16.4

16.8

 

 

 

 

 

TC

 

183

184

193

209

227

243

189

190

196

212

230

246

 

 

 

 

95

SHC

 

183

181

162

140

115

94

189

190

170

146

120

97

 

 

 

 

 

kW

 

16.8

16.8

17.1

17.6

18.0

18.4

17.0

17.0

17.2

17.6

18.1

18.5

 

 

 

 

 

TC

 

177

178

185

201

218

234

183

185

189

204

221

237

 

 

 

 

105

SHC

 

177

178

159

137

112

91

183

185

166

143

116

94

 

 

 

 

 

kW

 

18.6

18.6

18.8

19.3

19.8

20.2

18.8

18.6

18.9

19.4

19.9

20.3

 

 

 

 

 

TC

 

171

171

177

192

209

224

176

177

181

195

212

226

 

 

 

 

115

SHC

 

171

171

154

133

109

88

176

177

161

139

113

90

 

 

 

 

 

kW

 

20.5

20.5

20.7

21.2

21.8

22.1

20.7

20.7

20.8

21.3

21.8

22.2

 

 

 

 

 

TC

 

170

170

176

191

207

222

175

175

180

193

210

224

 

 

 

 

117

SHC

 

170

170

154

132

108

87

175

175

160

138

112

90

 

 

 

 

 

kW

 

20.9

20.9

21.1

21.6

22.1

22.5

21.1

21.1

21.2

21.7

22.2

22.6

 

 

 

 

 

TC

 

168

168

173

188

204

173

173

177

191

207

 

 

 

 

120

SHC

 

168

168

152

131

107

173

173

159

137

111

 

 

 

 

 

kW

 

21.5

21.5

21.7

22.2

22.7

21.7

21.7

21.8

22.3

22.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

579F216 (18 Tons) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm

 

 

 

 

 

 

 

 

 

Air Entering

 

 

 

 

7000

 

 

 

 

 

 

8000

 

 

 

 

300-

 

 

Condenser

 

 

 

 

 

 

Evaporator Air — Ewb (F)/BF

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54/0.58

58/0.42

62/0.29

67/0.21

72/0.20

76/0.20

80/0.05

54/0.62

58/0.48

62/0.36

67/0.23

72/0.22

76/0.21

80/0.04

 

 

 

 

 

 

 

 

579F180

 

 

75

TC

 

209

209

215

232

251

268

216

217

221

236

255

272

 

 

kW

 

15.5

15.5

15.7

16.1

16.5

16.9

15.7

15.7

15.8

16.2

16.6

17.0

 

 

 

 

SHC

 

209

209

189

162

132

106

216

217

198

171

138

109

 

 

 

 

 

kW

 

13.9

13.9

14.1

14.5

14.9

15.2

14.1

14.1

14.2

14.5

15.0

15.3

 

 

 

 

 

TC

 

203

204

209

224

243

260

211

211

215

228

247

263

 

 

 

 

85

SHC

 

203

204

185

159

129

103

211

211

192

168

135

107

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

197

197

202

216

235

251

204

204

209

220

238

254

 

 

 

 

95

SHC

 

197

197

180

156

126

100

204

204

185

165

132

104

 

 

 

 

 

kW

 

17.2

17.2

17.4

17.8

18.2

18.7

17.4

17.4

17.6

17.9

18.3

18.7

 

 

 

 

 

TC

 

191

191

195

208

225

241

197

197

202

211

228

244

 

 

 

 

105

SHC

 

191

191

175

152

123

97

197

197

177

161

128

100

 

 

 

 

 

kW

 

19.0

19.0

19.2

19.5

20.0

20.5

19.2

19.2

19.3

19.6

20.1

20.6

 

 

 

 

 

TC

 

184

184

188

199

215

230

190

190

194

202

218

 

 

 

 

115

SHC

 

184

184

168

149

119

94

190

190

170

158

125

 

 

 

 

 

kW

 

21.0

21.0

21.1

21.5

22.0

22.4

21.1

21.1

21.2

21.6

22.1

 

 

 

 

 

TC

 

183

183

187

197

214

228

188

188

192

200

216

 

 

 

 

117

SHC

 

183

183

166

148

118

93

188

188

171

157

124

 

 

 

 

 

kW

 

21.3

21.4

21.5

21.8

22.4

22.7

21.5

21.5

21.7

22.0

22.5

 

 

 

 

 

TC

 

180

180

185

194

210

186

186

190

197

 

 

 

 

120

SHC

 

180

180

163

147

117

186

186

172

156

 

 

 

 

 

kW

 

21.9

22.0

22.1

22.4

23.0

22.1

22.1

22.2

22.5

 

 

LEGEND

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb =

tedb

 

sensible capacity (Btuh)

 

 

1.10 x cfm

 

 

 

tlwb =

Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (hlwb)

 

hlwb =

hewb

total capacity (Btuh)

 

4.5 x cfm

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

FACTOR

81

82

83

84

85

over 85

(BF)

 

 

 

Correction Factor

 

0.05

1.04

2.07

3.11

4.14

5.18

 

0.10

0.98

1.96

2.94

3.92

4.91

 

0.20

0.87

1.74

2.62

3.49

4.36

 

0.30

0.76

1.53

2.29

3.05

3.82

Use formula

0.40

0.65

1.31

1.96

2.62

3.27

shown below.

0.50

0.55

1.09

1.64

2.18

2.73

 

0.60

0.44

0.87

1.31

1.74

2.18

 

0.70

0.33

0.65

0.98

1.31

1.64

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

154

Page 154
Image 154
Bryant 581A/B manual 154

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.