PERFORMANCE DATA (cont)

COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)

 

 

 

581B048 (4 TONS) — SUBCOOLING MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Ent

1200/0.17

 

 

 

 

1450/0.19

 

 

 

 

 

 

1600/0.21

 

 

 

 

 

2000/0.24

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

 

72

67

 

62

 

72

 

67

62

 

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

52.9

 

47.5

41.5

 

 

55.7

50.9

 

47.5

 

57.0

 

51.7

48.1

 

60.5

 

55.6

52.1

 

 

 

75

 

 

SHC

22.7

 

28.4

33.4

 

 

26.1

34.1

 

38.9

 

25.9

 

33.7

41.6

 

29.4

 

39.1

47.5

 

 

 

 

 

 

kW

2.87

 

2.86

2.82

 

 

2.89

2.87

 

2.84

 

2.89

 

2.86

2.85

 

2.90

 

2.88

2.85

 

 

 

 

 

 

TC

49.2

 

43.8

37.1

 

 

52.1

47.2

 

43.6

 

52.9

 

47.9

43.7

 

55.4

 

51.4

47.0

 

 

 

85

 

 

SHC

19.8

 

25.5

30.4

 

 

22.2

29.5

 

35.8

 

22.4

 

31.1

38.7

 

24.2

 

36.0

44.3

 

 

 

 

 

 

kW

3.26

 

3.25

3.21

 

 

3.28

3.26

 

3.23

 

3.28

 

3.26

3.24

 

3.28

 

3.26

3.24

 

 

 

 

 

 

TC

45.8

 

40.1

32.8

 

 

48.2

43.6

 

39.4

 

48.8

 

44.0

39.3

 

51.7

 

47.4

43.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

 

 

SHC

17.2

 

22.5

27.3

 

 

18.4

24.8

 

32.6

 

19.0

 

28.1

35.9

 

20.7

 

33.0

41.0

 

150

 

 

 

 

kW

3.71

 

3.68

3.64

 

 

3.72

3.69

 

3.67

 

3.72

 

3.69

3.67

 

3.74

 

3.70

3.68

 

 

105

 

 

TC

41.6

 

37.0

29.7

 

 

43.2

38.9

 

35.4

 

43.9

 

39.7

34.7

 

46.5

 

41.4

37.5

 

581B036-

 

 

 

SHC

13.5

 

19.5

23.9

 

 

14.7

21.7

 

29.2

 

15.0

 

23.7

30.6

 

16.4

 

27.8

35.1

 

 

 

 

 

kW

4.20

 

4.17

4.11

 

 

4.20

4.17

 

4.14

 

4.20

 

4.17

4.15

 

4.22

 

4.19

4.16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

37.2

 

33.2

27.1

 

 

38.4

34.0

 

30.8

 

39.4

 

35.5

30.0

 

41.3

 

35.2

31.9

 

 

 

115

 

 

SHC

9.9

 

16.4

20.7

 

 

11.3

18.5

 

25.6

 

11.2

 

19.7

25.4

 

12.4

 

22.4

28.6

 

 

 

 

 

 

kW

4.73

 

4.68

4.62

 

 

4.74

4.71

 

4.64

 

4.73

 

4.72

4.65

 

4.74

 

4.72

4.69

 

 

 

 

 

 

TC

32.4

 

28.1

24.9

 

 

33.8

28.1

 

27.4

 

35.3

 

30.5

26.6

 

36.1

 

32.0

28.7

 

 

 

125

 

 

SHC

7.2

 

12.9

18.3

 

 

8.4

14.5

 

21.9

 

16.8

 

21.1

21.2

 

9.5

 

18.3

24.1

 

 

 

 

 

 

kW

5.29

 

5.23

5.15

 

 

5.30

5.25

 

5.19

 

5.29

 

5.27

5.21

 

5.30

 

5.29

5.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B048 (4 TONS) — HOT GAS REHEAT MODE*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

75 Dry Bulb

 

 

 

 

 

75 Dry Bulb

 

 

 

 

 

75 Dry Bulb

 

 

 

 

 

 

Air Ent

 

 

 

62.5 Wet Bulb

 

 

 

 

 

64 Wet Bulb

 

 

 

 

65.3 Wet Bulb

 

 

 

 

 

Condenser

 

 

 

(50% Relative)

 

 

 

 

(55% Relative)

 

 

 

 

(60% Relative)

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Cfm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1200

 

 

1450

 

 

1600

 

1200

 

 

1450

 

1600

 

1200

 

 

 

1450

 

1600

 

 

 

 

 

 

TC

 

12.13

 

 

14.30

 

 

15.43

 

14.98

 

 

17.20

 

18.36

 

17.44

 

 

19.71

 

20.90

 

 

 

80

 

 

SHC

 

1.01

 

 

1.60

 

 

1.90

 

–0.18

 

 

0.41

 

0.72

 

–1.20

 

 

–0.61

 

–0.30

 

 

 

 

 

 

kW

 

2.76

 

 

2.76

 

 

2.76

 

2.75

 

 

2.75

 

2.75

 

2.74

 

 

 

2.74

 

2.74

 

 

 

 

 

 

TC

 

13.25

 

 

15.28

 

 

16.34

 

15.96

 

 

18.05

 

19.14

 

18.31

 

 

20.44

 

21.56

 

 

 

75

 

 

SHC

 

1.60

 

 

2.14

 

 

2.43

 

0.50

 

 

1.05

 

1.34

 

–0.45

 

 

0.11

 

0.40

 

 

 

 

 

 

kW

 

7.54

 

 

7.54

 

 

7.57

 

7.61

 

 

7.64

 

7.66

 

7.66

 

 

 

7.70

 

7.71

 

 

 

 

 

 

TC

 

14.37

 

 

16.27

 

 

17.26

 

16.94

 

 

18.90

 

19.92

 

19.17

 

 

21.17

 

22.22

 

 

 

70

 

 

SHC

 

2.18

 

 

2.69

 

 

2.96

 

1.17

 

 

1.69

 

1.96

 

0.30

 

 

0.82

 

1.10

 

 

 

 

 

 

kW

 

2.70

 

 

2.70

 

 

2.70

 

2.70

 

 

2.70

 

2.70

 

2.70

 

 

 

2.70

 

2.70

 

 

 

 

 

 

TC

 

16.60

 

 

18.24

 

 

19.10

 

18.91

 

 

20.60

 

21.48

 

20.91

 

 

22.64

 

23.54

 

 

 

60

 

 

SHC

 

3.35

 

 

3.79

 

 

4.03

 

2.52

 

 

2.97

 

3.21

 

1.80

 

 

2.25

 

2.50

 

 

 

 

 

 

kW

 

2.64

 

 

2.64

 

 

2.64

 

2.65

 

 

2.65

 

2.65

 

2.65

 

 

 

2.65

 

2.65

 

 

 

 

 

 

TC

 

18.83

 

 

20.22

 

 

20.94

 

20.87

 

 

22.30

 

23.04

 

22.65

 

 

24.10

 

24.86

 

 

 

50

 

 

SHC

 

4.51

 

 

4.89

 

 

5.09

 

3.86

 

 

4.25

 

4.45

 

3.30

 

 

3.69

 

3.89

 

 

 

 

 

 

kW

 

2.59

 

 

2.59

 

 

2.59

 

2.60

 

 

2.60

 

2.60

 

2.61

 

 

 

2.61

 

2.61

 

 

 

 

 

 

TC

 

21.06

 

 

22.19

 

 

22.78

 

22.84

 

 

24.00

 

24.61

 

24.38

 

 

25.57

 

26.19

 

 

 

40

 

 

SHC

 

5.68

 

 

5.99

 

 

6.16

 

5.21

 

 

5.53

 

5.69

 

4.80

 

 

5.12

 

5.29

 

 

 

 

 

 

kW

 

2.53

 

 

2.53

 

 

2.53

 

2.55

 

 

2.55

 

2.55

 

2.57

 

 

 

2.57

 

2.57

LEGEND

BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet Bulb

kW — Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross TC — Total Capacity (1000 Btuh) Gross

*Negative SHC value indicates that the air entering the coil is being heated.

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.

2. The following formulas may be used:

tldb

=

tedb

 

sensible capacity (Btuh)

 

 

1.10 x cfm

 

 

 

 

 

tlwb

= Wet-bulb temperature corresponding to enthalpy of air

 

 

leaving evaporator coil (hlwb)

hlwb

=

hewb

 

total capacity (Btuh)

 

 

4.5 x cfm

 

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil.

3.The SHC is based on 80 F edb temperature of air entering evapo- rator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 – BF) x (edb – 80).