PERFORMANCE DATA (cont)

COOLING CAPACITIES — STANDARD UNITS (cont)

581A210 (18 Tons)

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

Evap Air — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5400/0.05

 

 

 

 

 

 

6300/0.06

 

 

 

 

 

 

7200/0.07

 

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

Cond

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

58

62

 

67

 

72

76

80

54

58

62

 

67

 

72

76

80

54

58

62

 

67

 

72

76

80

 

TC

202

206

211

 

229

 

248

263

279

212

215

218

 

235

 

254

269

285

220

221

223

 

239

 

259

273

289

60

SHC

202

193

184

 

155

 

124

99.3

74.7

212

205

199

 

166

 

131

103

74.9

220

216

213

 

177

 

138

106

75

 

kW

10.2

10.3

10.4

 

10.6

 

10.8

11

11.2

10.4

10.4

10.4

 

10.7

 

10.9

11.1

11.3

10.5

10.5

10.5

 

10.7

 

11

11.2

11.4

 

TC

197

202

206

 

223

 

242

256

272

207

209

212

 

228

 

247

262

277

215

216

217

 

233

 

252

267

282

70

SHC

197

189

181

 

152

 

122

97

72.5

207

202

196

 

163

 

129

101

72.7

215

212

210

 

174

 

135

104

72.8

 

kW

11.4

11.5

11.5

 

11.8

 

12

12.2

12.5

11.6

11.6

11.6

 

11.9

 

12.1

12.3

12.6

11.7

11.7

11.7

 

11.9

 

12.2

12.4

12.6

 

TC

195

199

203

 

219

 

238

253

268

204

206

209

 

225

 

244

258

273

212

213

214

 

229

 

248

263

277

75

SHC

195

187

180

 

150

 

120

95.8

71.3

204

199

195

 

162

 

127

99.3

71.4

212

210

208

 

173

 

134

103

71.5

 

kW

12.1

12.2

12.2

 

12.5

 

12.7

13

13.2

12.3

12.3

12.3

 

12.6

 

12.8

13

13.3

12.4

12.4

12.4

 

12.6

 

12.9

13.1

13.3

 

TC

190

193

196

 

213

 

231

246

260

199

201

202

 

218

 

236

251

264

206

207

208

 

222

 

240

255

268

85

SHC

190

183

177

 

148

 

118

93.4

68.8

199

195

191

 

159

 

125

96.9

68.9

206

205

204

 

170

 

131

100

69

 

kW

13.5

13.5

13.6

 

13.8

 

14.1

14.4

14.6

13.6

13.7

13.7

 

13.9

 

14.2

14.5

14.7

13.7

13.8

13.8

 

14

 

14.3

14.5

14.8

 

TC

184

187

190

 

205

 

222

236

250

193

194

195

 

210

 

227

241

254

200

200

201

 

214

 

231

245

258

95

SHC

184

179

173

 

144

 

114

90.2

65.9

193

190

187

 

156

 

121

93.7

66.1

200

199

199

 

167

 

128

97.1

66.2

 

kW

15

15

15.1

 

15.4

 

15.7

15.9

16.2

15.1

15.2

15.2

 

15.5

 

15.8

16

16.3

15.3

15.3

15.3

 

15.5

 

15.8

16.1

16.3

 

TC

178

180

182

 

197

 

213

228

240

186

187

188

 

201

 

217

232

244

193

193

193

 

205

 

221

235

247

105

SHC

178

173

169

 

141

 

111

87.3

62.9

186

184

183

 

152

 

118

90.8

63.1

193

193

193

 

163

 

124

94.1

63.2

 

kW

16.6

16.7

16.7

 

17

 

17.3

17.7

17.9

16.8

16.8

16.8

 

17.1

 

17.4

17.8

18

16.9

16.9

16.9

 

17.2

 

17.5

17.8

18

 

TC

171

172

174

 

188

 

203

217

228

179

179

179

 

192

 

207

221

232

185

185

185

 

195

 

210

224

235

115

SHC

171

168

165

 

137

 

107

83.6

59.6

179

178

178

 

149

 

114

87.1

59.7

185

185

185

 

159

 

121

90.4

59.9

 

kW

18.4

18.4

18.4

 

18.8

 

19.1

19.4

19.7

18.6

18.6

18.6

 

18.9

 

19.2

19.5

19.8

18.7

18.7

18.7

 

19

 

19.3

19.6

19.9

 

TC

164

165

165

 

178

 

192

205

216

171

171

171

 

182

 

196

208

219

177

177

177

 

185

 

199

211

222

125

SHC

164

162

160

 

134

 

104

79.8

56.1

171

171

171

 

145

 

110

83.2

56.3

177

177

177

 

155

 

117

86.5

56.4

 

kW

20.2

20.3

20.3

 

20.6

 

21

21.3

21.6

20.4

20.4

20.4

 

20.8

 

21.1

21.4

21.7

20.6

20.6

20.6

 

20.8

 

21.2

21.5

21.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581A210 (18 Tons) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

Evap Air — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8100/0.08

 

 

 

 

 

 

9000/0.09

 

 

 

 

 

 

 

 

 

 

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cond

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

58

62

 

67

 

72

76

80

54

58

62

 

67

 

72

76

80

 

 

 

 

 

 

 

 

 

 

TC

227

227

228

 

243

 

262

277

293

233

233

233

 

246

 

265

280

295

 

 

 

 

 

 

 

 

 

60

SHC

227

226

224

 

187

 

144

109

75.1

233

233

233

 

198

 

151

113

75.1

 

 

 

 

 

 

 

 

 

 

kW

10.5

10.6

10.6

 

10.7

 

11

11.2

11.4

10.6

10.6

10.6

 

10.8

 

11

11.3

11.5

 

 

 

 

 

 

 

 

 

 

TC

222

222

222

 

236

 

255

271

284

228

228

227

 

239

 

258

272

287

 

 

 

 

 

 

 

 

 

70

SHC

222

221

221

 

185

 

142

107

72.8

228

228

227

 

195

 

148

110

72.9

 

 

 

 

 

 

 

 

 

 

kW

11.8

11.8

11.8

 

12

 

12.2

12.5

12.7

11.9

11.9

11.8

 

12

 

12.3

12.5

12.7

 

 

 

 

 

 

 

 

 

 

TC

219

219

219

 

232

 

251

266

280

225

224

224

 

235

 

254

268

282

 

 

 

 

 

 

 

 

 

75

SHC

219

218

218

 

183

 

140

106

71.6

225

224

224

 

193

 

147

109

71.7

 

 

 

 

 

 

 

 

 

 

kW

12.5

12.5

12.5

 

12.7

 

12.9

13.2

13.4

12.6

12.5

12.5

 

12.7

 

13

13.2

13.4

 

 

 

 

 

 

 

 

 

 

TC

213

213

213

 

225

 

243

258

271

218

218

218

 

228

 

245

260

273

 

 

 

 

 

 

 

 

 

85

SHC

213

213

213

 

180

 

138

103

69.1

218

218

218

 

190

 

144

107

69.2

 

 

 

 

 

 

 

 

 

 

kW

13.8

13.8

13.8

 

14.1

 

14.3

14.6

14.8

13.9

13.9

13.9

 

14.1

 

14.4

14.6

14.8

 

 

 

 

 

 

 

 

 

 

TC

206

206

206

 

217

 

234

248

260

211

211

211

 

220

 

236

250

262

 

 

 

 

 

 

 

 

 

95

SHC

206

206

206

 

177

 

134

100

66.3

211

211

211

 

187

 

141

103

66.4

 

 

 

 

 

 

 

 

 

 

kW

15.4

15.4

15.4

 

15.6

 

15.9

16.1

16.4

15.5

15.5

15.5

 

15.6

 

15.9

16.2

16.4

 

 

 

 

 

 

 

 

 

 

TC

199

199

199

 

208

 

224

238

249

203

203

204

 

210

 

226

240

251

 

 

 

 

 

 

 

 

 

105

SHC

199

199

199

 

173

 

131

97.2

63.2

203

203

204

 

183

 

137

100

63.4

 

 

 

 

 

 

 

 

 

 

kW

17

17.1

17.1

 

17.3

 

17.6

17.9

18.1

17.2

17.2

17.2

 

17.3

 

17.6

17.9

18.1

 

 

 

 

 

 

 

 

 

 

TC

191

191

191

 

198

 

213

226

237

195

195

195

 

201

 

215

228

238

 

 

 

 

 

 

 

 

 

115

SHC

191

191

191

 

169

 

127

93.5

60

195

195

195

 

179

 

133

96.6

60

 

 

 

 

 

 

 

 

 

 

kW

18.8

18.8

18.8

 

19

 

19.3

19.7

19.9

18.9

18.9

18.9

 

19.1

 

19.4

19.7

19.9

 

 

 

 

 

 

 

 

 

 

TC

182

182

182

 

188

 

201

213

224

186

186

186

 

190

 

203

215

225

 

 

 

 

 

 

 

 

 

125

SHC

182

182

182

 

165

 

123

89.6

56.5

186

186

186

 

174

 

129

92.6

56.6

 

 

 

 

 

 

 

 

 

 

kW

20.7

20.7

20.7

 

20.9

 

21.2

21.6

21.9

20.9

20.9

20.9

 

21

 

21.3

21.6

21.9

 

 

 

 

 

 

 

 

 

581A155-300

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

 

1. Direct interpolation is permissible. Do not extrapolate.

2. The following formulas may be used:

tldb

= tedb

 

sensible capacity (Btuh)

 

 

 

1.10 x cfm

 

 

 

 

 

tlwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

 

 

rator coil (hlwb)

hlwb

= hewb

total capacity (Btuh)

 

4.5 x cfm

 

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

 

76

75

 

under 75

FACTOR

 

 

81

82

83

 

84

85

 

over 85

(BF)

 

 

 

 

 

 

 

Correction

Factor

 

 

.05

1.04

2.07

3.11

 

4.14

5.18

 

 

.10

.98

1.96

2.94

 

3.92

4.90

 

Use formula

.20

.87

1.74

2.62

 

3.49

4.36

 

shown below.

.30

.76

1.53

2.29

 

3.05

3.82

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

 

 

 

ENTERING WET-BULB (F)

 

 

CFM

54

58

62

67

72

76

80

 

 

 

Bypass Factor

 

 

5400

0.424

0.238

0.125

0.120

0.138

0.000

0.000

6300

0.478

0.304

0.153

0.132

0.145

0.000

0.000

7200

0.525

0.364

0.190

0.144

0.153

0.000

0.000

8100

0.562

0.414

0.231

0.156

0.162

0.000

0.000

9000

0.594

0.456

0.281

0.168

0.170

0.000

0.000

210

Page 210
Image 210
Bryant 581A/B manual 210

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.