GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)

580F036-150 AND 581B036-150

t. Remote Minimum Position Control — A field- installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation.

3. Manual Outdoor-Air Damper:

Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for year round ventilation.

*4. 100% Two-Position Damper:

a.Two-position damper package shall include single blade damper and motor. Admits up to 100% out- door air.

b.Damper shall close upon indoor (evaporator) fan shutoff.

c.Designed to close damper during loss of power situations.

d.Equipped with 15% barometric relief damper.

*5. 25% Two-Position Damper:

a.Two-position damper package shall include single blade damper and motor. Admits up to 25% out- door air.

b.Damper shall close upon indoor (evaporator) fan shutoff.

*6. Head Pressure Control Package:

Consists of solid-state control and condenser-coil temperature sensor to maintain condensing temper- ature between 90 F and 110 F at outdoor ambient temperatures down to –20 F by condenser-fan speed modulation or condenser-fan cycling and wind baffles.

7. LP (Liquid Propane) Conversion Kit:

Package shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane (valid up to 2000 ft elevation).

*8. Electronic Programmable Thermostat:

Units shall be capable of using deluxe full-featured electronic thermostat. Thermostat shall use built-in compressor cycle delay control for both heating and cooling duty. Thermostat shall be capable of working with third party direct digital controls.

9. Light Commercial Thermidistat™ Device:

Field-installed wall-mounted thermostat is used to control temperature and activation of the dehumidifi- cation package. The Thermidistat device can be set for humidity settings from 50% to 90% relative humidity. Automatic humidity control adjusts indoor humidity based on the outdoor temperature sensor.

*10. Flue Shield:

Flue shield shall provide protection from the hot sides of the gas flue hood.

*11. Thermostat and Subbase:

Thermostat and subbase shall provide staged cool- ing and heating automatic (or manual) changeover, fan control, and indicator light.

*12. Condenser Coil Hail Guard Assembly:

Hail guard shall protect against damage from hail and flying debris.

13. Unit-Mounted, Non-Fused Disconnect Switch:

Switch shall be factory-installed, internally mounted. NEC and UL approved non-fused switch shall

provide unit power shutoff. Switch shall be accessi- ble from outside the unit and shall provide power off lockout capability.

14. Convenience Outlet:

Outlet shall be factory-installed and internally mounted with easily accessible 115-v female recep- tacle. Shall include 15 amp GFI receptacle with inde- pendent fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed step-down transformer. Shall be accessible from outside the unit.

15.High-Static Indoor Fan Motor(s) and Drive(s)

(036-120):

High-static motor(s) and drive(s) shall be factory- installed to provide additional performance range.

16. Flue Discharge Deflector:

Flue discharge deflector directs unit exhaust verti- cally instead of horizontally.

17. Condenser Coil Grille:

The grille protects the condenser coil from damage by large objects without increasing unit clearances.

18. Compressor Cycle Delay:

Unit shall be prevented from restarting for minimum of 5 minutes after shutdown.

19. Thru-the-Bottom Utility Connectors:

Kit shall provide connectors to permit gas and elec- trical connections to be brought to the unit through the basepan.

20. Fan/Filter Status Switch:

Switch shall provide status of indoor (evaporator) fan (ON/OFF) or filter (CLEAN/DIRTY). Status shall be displayed over communication bus when used with direct digital controls or with an indicator light at the thermostat.

21.Power Exhaust Accessory for EconoMi$er IV or EconoMi$er2:

Power exhaust shall be used in conjunction with EconoMi$er IV or EconoMi$er2 to provide system exhaust of up to 100% of return air (vertical only). The power exhaust is a field-installed accessory (separate vertical and horizontal design).

NOTE: Horizontal power exhaust is intended to mount in return ductwork.

As the outdoor-air damper opens and closes, both propeller fans are energized and deenergized through the EconoMi$er IV controller. The set point is factory set at 100% of outdoor-air, and is adjust- able 0 to 100% to meet specific job requirements. Available in 208/230-1-60 v or 460-3-60 v. An LED light on the controller indicates when the power exhaust is operating.

For the EconoMi$er2, the power exhaust shall be controlled by the third party controls.

22.Outdoor Air Enthalpy Sensor (EconoMi$er IV or EconoMi$er2):

The outdoor air enthalpy sensor shall be used with the EconoMi$er IV or EconoMi$er2 device to provide single enthalpy control. When used in conjunction with a return air enthalpy sensor, the EconoMi$er IV or EconoMi$er2 device will provide differential enthalpy control. The sensor allows the EconoMi$er IV or EconoMi$er2 controller to determine if outside air is suitable for free cooling.

142

Page 142
Image 142
Bryant 581A/B manual 142

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.