Bryant 581A/B manual Altitude COMPENSATION* 581B036-072, Altitude COMPENSATION* 581B090-150

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 127
Image 127

PERFORMANCE DATA (cont)

FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581B036-150

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

581B

0

1/2

1

11/2

2

 

21/2

3

31/2

 

4

41/2

5

51/2

6

036

1044

1008

971

935

898

 

862

826

789

 

753

716

680

048

1185

1144

1102

1061

1019

 

978

936

895

 

853

812

770

060

1460

1425

1389

1354

1318

 

1283

1248

1212

 

1177

1141

1106

1070

1035

072

1585

1538

1492

1445

1399

 

1352

1305

1259

 

1212

1166

1119

090,102

1085

1060

1035

1010

985

 

960

935

910

 

890

865

840

120

1080

1060

1035

1015

990

 

970

950

925

 

905

880

860

150

1130

1112

1087

1062

1037

 

1212

987

962

 

937

912

887

962

830

*Approximate fan rpm shown (standard motor/drive).

FAN RPM AT MOTOR PULLEY SETTING WITH HIGH-STATIC MOTOR* — 581B036-150

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

581B

0

1/2

1

11/2

2

 

21/2

3

31/2

 

4

41/2

5

51/2

6

036

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

048

1455

1423

1392

1360

1328

 

1297

1265

1233

 

1202

1170

1138

1107

1075

060

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

072

1685

1589

1557

1525

1493

 

1460

1428

1396

 

1364

1332

1300

090

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

102

1080

1025

1007

988

970

 

952

933

915

 

897

878

860

120

1130

1112

1087

1062

1037

 

1212

987

962

 

937

912

887

962

830

*Approximate fan rpm shown (high-static motor/drive).

581B036-150

ALTITUDE COMPENSATION* — 581B036-072

 

72,000 AND 115,000/

150,000/120,000 BTUH

 

60,000 and 90,000 BTUH

 

NOMINAL INPUT

ELEVATION

NOMINAL INPUT

 

 

(ft)

Natural Gas

Liquid

Natural

Liquid

 

Propane

Gas

Propane

 

Orifice Size†

 

Orifice Size†

Orifice Size

Orifice Size†

0-2,000

33/38

43

30/32

38

2,000

34/39

43

30/33

39

3,000

35/40

44

31/34

40

4,000

36/41

44

32/35

41

5,000

36/41

44

33/35

42

6,000

37/42

45

34/36

43

7,000

37/42

45

35/37

43

8,000

38/43

46

36/37

44

9,000

39/43

47

37/38

44

10,000

41/44

48

38/40

45

11,000

43/45

48

39/41

45

12,000

44/45

49

40/42

46

13,000

44/46

49

41/43

47

14,000

45/47

50

42/43

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes.

†Orifices are available through your local Bryant distributor.

ALTITUDE COMPENSATION* — 581B090-150

 

125,000, 180,000, AND

250,000 BTUH

 

224,000 BTUH

 

NOMINAL INPUT

ELEVATION

NOMINAL INPUT

 

 

(ft)

Natural Gas

Liquid

Natural Gas

Liquid

 

Orifice

Propane

Orifice

Propane

 

Size†

Orifice Size†

Size†

Orifice Size†

0-2,000

31

41

30

38

2,000

32

42

30

39

3,000

32

42

31

40

4,000

32

42

32

41

5,000

33

43

33

42

6,000

34

43

34

43

7,000

35

44

35

43

8,000

36

44

36

44

9,000

37

45

37

44

10,000

38

46

38

45

11,000

39

47

39

45

12,000

40

47

40

46

13,000

41

48

41

47

14,000

42

48

42

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes.

†Orifices are available through your local Bryant distributor.

ALTITUDE DERATING FACTOR*

ELEVATION

MAXIMUM HEATING VALUE (Btu/ft3)

0-2000

1100

2001-3000

1050

3001-4000

1000

4001-5000

950

5001-6000

900

*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.

127