GUIDE SPECIFICATIONS — 581A210-300 UNITS

PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATION

HVAC GUIDE SPECIFICATIONS

SIZE RANGE: 18 TO 25 TONS NOMINAL (COOLING)

250,000 TO 400,000 BTUH, NOMINAL (INPUT HEATING)

BRYANT MODEL NUMBERS: 581A

PART 1 — GENERAL

1.01SYSTEM DESCRIPTION

Unit is an outdoor rooftop mounted, electrically controlled heating and cooling unit utilizing scroll hermetic compres- sors with crankcase heaters for cooling duty and gas com- bustion heat for heating duty. Supply air shall be discharged downward or horizontally, as shown on con- tract drawings.

1.02QUALITY ASSURANCE

A.Unit shall well exceed the energy efficiency requirements of ASHRAE standard 90.1-2001. Unit shall be Energy Star qualified.

B.Unit shall be rated in accordance with ARI Standards 270 and 360 and all units shall be designed in accordance with UL Standard 1995.

C.Unit shall be designed to conform to ASHRAE 15.

D.Unit shall be UL and UL, Canada, tested and certified in accordance with ANSI Z21.47 Standards as a total package.

E.Roof curb shall be designed to conform to NRCA Standards.

F.Insulation and adhesive shall meet NFPA 90A require- ments for flame spread and smoke generation.

G.Unit casing shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).

H.Unit shall be manufactured in a facility registered to ISO 9001:2000.

1.03 DELIVERY, STORAGE, AND HANDLING

Unit shall be stored and handled per manufacturer’s recommendations.

PART 2 — PRODUCTS

2.01EQUIPMENT (STANDARD)

A.General:

The 581A unit shall be a factory assembled, single-piece heating and cooling unit. Contained within the unit enclo- sure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up.

B.Unit Cabinet:

fiberglass insulation. Fiberglass insulation shall be bonded with a thermosetting resin (8 to 12% by weight nominal, phenol formaldehyde typical), and coated with an acrylic or other material that meets the NFPA 90 flame retardance requirements and has an ‘‘R’’ Value of 3.70. Aluminum foil-faced fiber- glass insulation shall be used in the gas heat compartment.

3.Cabinet panels shall have minimum 1/2-in. thick, 1.5-lb. density insulation. Each external access panel shall be permanently attached to the rooftop unit. Panels shall also include tiebacks.

4.Filters shall be accessible through an access panel.

5.Holes shall be provided in the base rails (minimum 14 gage) for rigging shackles and level travel and movement during overhead rigging operations.

6.Fork lift slots shall be available from two sides of the unit (end and side).

7.Unit shall contain a sloped drain pan, to prevent standing water from accumulating. Pan shall be fabri- cated of epoxy powder coated steel.

C.Fans:

1.Indoor blower (evaporator fan):

a.Centrifugal supply air blower shall have pillow- block ball bearings and adjustable belt drive. Blower assembly shall slide out of unit for servicing.

b.Fan wheel shall be made from steel with a corro- sion resistant finish. It shall be a dynamically bal- anced, double-inlet type with forward-curved blades.

c.The indoor fan system (blower wheels, motors, belts, and both bearings) shall slide out for easy access.

2.Condenser fans shall be of the direct-driven propeller type, with corrosion-resistant blades riveted to corro- sion-resistant steel supports. They shall be dynami- cally balanced and discharge air upwards. Condenser fan motors shall be totally enclosed and be of a shaft down design.

3.Induced-draft blower shall be of the direct-driven, sin- gle inlet, forward-curved, centrifugal type. It shall be made from steel with a corrosion-resistant finish and shall be dynamically balanced.

D.Compressor(s):

1.Fully hermetic, scroll type, internally protected.

2.Factory spring-shock mounted and internally spring mounted for vibration isolation.

3.On electrically and mechanically independent refrig- erant circuits.

4.Reverse rotation protection capability.

5.Crankcase heaters shall only be activated during compressor OFF mode.

E.Coils:

1.

Constructed of galvanized steel (G90 — 1.8 oz. of

1.

Standard evaporator and condenser coils shall have

 

zinc per square foot of sheet metal), bonderized and

 

copper or aluminum plate fins mechanically bonded

 

primer-coated on both sides and coated with a baked

 

to seamless internally grooved copper tubes with all

 

polyester thermosetting powdercoating finish on the

 

joints brazed.

 

outer surface.

2.

Coils shall be leak tested at 150 psig (1034 kPa) and

2.

Indoor blower compartment interior surfaces shall be

 

pressure tested at 450 psig (3103 kPa).

 

insulated with a minimum 1/ -in. thick, 1 lb density

 

 

 

2

 

 

581A210-300

255

Page 255
Image 255
Bryant 581A/B manual Guide Specifications 581A210-300 Units

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.