Bryant 581A/B ARI* Capacity Ratings 581B036-150, Heating Capacities and Efficiencies 581B036-150

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 10
Image 10

ARI* CAPACITY RATINGS — 581B036-150

UNIT

NOMINAL

COOLING

TOTAL

SEER†

EER

SOUND RATING

IPLV

581B

TONS

(Btuh)

kW

dB

 

 

 

036

3

36,000

3.21

13.0

11.20

76

**

048

4

46,000

4.25

13.0

11.05

76

**

060

5

61,000

5.55

13.0

11.00

80

**

072

6

73,000

6.70

11.00

80

**

090

71/2

90,000

8.18

11.00

82

11.6

102

81/2

103,000

8.90

11.60

82

12.8

120

10

120,000

10.91

11.00

84

11.4

150

121/2

138,000

14.40

9.6

86

10.3

LEGEND

EER — Energy Efficiency Ratio

IPLV — Integrated Part-Load Value

SEER — Seasonal Energy Efficiency Ratio

*Air-Conditioning & Refrigeration Institute.

†Applies only to units with capacity of 65,000 Btuh or less. **The IPLV is not applicable to single-compressor units.

NOTES:

1.Rated in accordance with ARI Standard 210/240 (036-120 units) or 360 (150 units) and 270 (036-150 units).

2.Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:

Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db outdoor entering-air temperature.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

Sizes 036-120

Sizes 150

Only

Only

3.All 581B036-150 units are in compliance with ASHRAE 90.1-1999 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website: http://sol- stice.crest.org/efficiency/bcap to determine if compliance with this standard pertains to a given geographical area of the United States.

4.All 581B036-120 units are Energy Star certified.

HEATING CAPACITIES AND EFFICIENCIES — 581B036-150

208/230-1-60SINGLE-STAGE GAS HEAT

UNIT

INPUT CAPACITY

OUTPUT CAPACITY

TEMPERATURE

MINIMUM HEATING

EFFICIENCY

581B

RISE (°F)

AIRFLOW (CFM)

AFUE (%)

Steady State (%)

 

 

036072

72,000

58,000

25-55

1004

82.8

82.0

036115

115,000

90,000

55-85

1002

80.0

80.0

048072

72,000

58,000

25-55

1004

82.8

82.0

048115

115,000

90,000

35-65

1320

81.0

81.0

048150

150,000

118,000

50-80

1396

80.4

80.0

060072

72,000

58,000

25-55

1004

82.8

82.0

060115

115,000

92,000

35-65

1327

81.0

81.0

060150

150,000

118,000

50-80

1314

80.4

80.0

 

LEGEND

 

 

 

 

 

AFUE — Annual Fuel Utilization Efficiency.

 

 

 

 

 

 

208/230-1-60SINGLE-STAGE GAS HEAT — LOW NOx

 

 

 

 

 

 

 

 

UNIT

INPUT CAPACITY

OUTPUT CAPACITY

TEMPERATURE

MINIMUM HEATING

EFFICIENCY

581B

RISE (°F)

AIRFLOW (CFM)

AFUE (%)

Steady State (%)

 

 

036060N

60,000

50,000

20-50

930

80.2

81.2

036090N

90,000

74,000

30-60

1150

81.0

81.4

048060N

60,000

50,000

20-50

930

80.2

81.2

048090N

90,000

74,000

30-60

1150

81.0

81.4

048120N

120,000

101,000

40-70

1340

80.7

82.4

060060N

60,000

50,000

20-50

930

80.2

81.2

060090N

90,000

74,000

30-60

1150

81.0

81.4

060120N

120,000

101,000

40-70

1340

80.7

82.4

LEGEND

AFUE — Annual Fuel Utilization Efficiency.

10

Page 10
Image 10
Bryant 581A/B manual ARI* Capacity Ratings 581B036-150, Heating Capacities and Efficiencies 581B036-150

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.