PERFORMANCE DATA (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS

581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)*

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

900

567

0.15

145

688

0.22

222

786

0.30

296

871

0.37

368

947

0.44

437

 

 

 

1000

599

0.18

177

717

0.27

265

814

0.35

349

897

0.43

430

972

0.51

509

 

 

 

1100

632

0.22

215

747

0.31

313

842

0.41

407

925

0.50

498

999

0.59

587

 

 

 

1200

666

0.26

257

778

0.37

367

871

0.47

471

952

0.57

572

1025

0.67

670

 

 

 

1300

701

0.31

306

810

0.43

426

901

0.54

540

981

0.65

651

1053

0.76

760

 

 

 

1400

737

0.36

361

842

0.49

491

931

0.62

616

1010

0.74

738

1081

0.86

856

 

 

 

1500

773

0.42

422

875

0.57

564

963

0.70

699

1040

0.84

831

1110

0.96

960

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B036 (3 TONS) — STANDARD MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

581B036

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

900

1016

0.51

505

1080

0.57

572

1139

0.64

637

1195

0.71

702

1249

0.77

765

 

-150

 

1000

1041

0.59

587

1104

0.67

662

1163

0.74

737

1219

0.81

811

1272

0.89

883

 

 

1100

1066

0.68

674

1129

0.76

759

1188

0.85

843

1243

0.93

925

1296

1.01

1007

 

 

1200

1093

0.77

767

1155

0.87

861

1213

0.96

955

1268

1.05

1047

1321

1.14

1137

 

 

 

1300

1119

0.87

866

1181

0.98

970

1239

1.08

1073

1294

1.18

1175

 

 

 

1400

1147

0.98

972

1208

1.09

1086

 

 

 

1500

1175

1.09

1086

 

 

 

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Motor drive range: 680 to 1044 rpm. All other rpms require field- supplied drive.

Refer to this page for general Fan Performance Data notes.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 1.20.

581B048 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

567

0.15

145

688

0.22

222

 

786

0.30

296

871

0.37

368

947

0.44

437

1000

599

0.18

177

717

0.27

265

 

814

0.35

349

897

0.43

430

972

0.51

509

1100

632

0.22

215

747

0.31

313

 

842

0.41

407

925

0.50

498

999

0.59

587

1200

666

0.26

257

778

0.37

367

 

871

0.47

471

952

0.57

572

1025

0.67

670

1300

701

0.31

306

810

0.43

426

 

901

0.54

540

981

0.65

651

1053

0.76

760

1400

737

0.36

361

842

0.49

491

 

931

0.62

616

1010

0.74

738

1081

0.86

856

1500

773

0.42

422

875

0.57

564

 

963

0.70

699

1040

0.84

831

1110

0.96

960

 

 

 

 

 

 

 

 

 

 

581B048 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

1016

0.51

505

1080

0.57

572

 

1139

0.64

637

1195

0.71

702

1249

0.77

765

1000

1041

0.59

587

1104

0.67

662

 

1163

0.74

737

1219

0.81

811

1272

0.89

883

1100

1066

0.68

674

1129

0.76

759

 

1188

0.85

843

1243

0.93

925

1296

1.01

1007

1200

1093

0.77

767

1155

0.87

861

 

1213

0.96

955

1268

1.05

1047

1321

1.14

1137

1300

1119

0.87

866

1181

0.98

970

 

1239

1.08

1073

1294

1.18

1175

1346

1.28

1275

1400

1147

0.98

972

1208

1.09

1086

 

1265

1.21

1199

1320

1.32

1310

1371

1.43

1419

1500

1175

1.09

1086

1235

1.22

1209

 

1292

1.34

1332

1346

1.46

1452

1397

1.58

1572

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Motor drive range: 1075 to 1455 rpm. All other rpms require field- supplied drive.

Refer to this page for general Fan Performance Data notes.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1.Static pressure losses (i.e., EconoMi$er IV) must be added to external static pressure before entering Fan Performance table.

2.Interpolation is permissible. Do not extrapolate.

3.Fan performance is based on wet coils, clean filters, and casing losses. See Accessory/FIOP Static Pressure table on page 128.

4.Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with

confidence. Using the fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor fail- ure. Unit warranty will not be affected.

5.Use of a field-supplied motor may affect wire size. Contact your Bryant representative for details.

103

Page 103
Image 103
Bryant 581A/B manual 581B036 3 Tons Standard Motor Belt Drive, 581B048 3 Tons HIGH-STATIC Motor Belt Drive

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.