PERFORMANCE DATA — 579F (cont)

COOLING CAPACITIES (cont)

 

 

 

 

579F300 (25 Tons)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm

 

 

 

 

 

 

 

 

 

Air Entering

 

 

 

 

7,000

 

 

 

 

 

 

8,000

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

Evaporator Air — Ewb (F)/BF

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54/0.44

58/0.26

62/0.13

67/0.12

72/0.12

76/0.19

80/0.01

54/0.49

58/0.32

62/0.15

67/0.14

72/0.13

76/0.17

80/0.00

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

256

270

298

325

349

370

266

268

280

304

324

352

379

 

 

 

 

75

SHC

 

243

229

198

164

133

106

266

251

246

209

168

137

107

 

 

 

 

 

kW

 

19.3

20.0

20.3

21.0

21.6

22.2

19.5

19.6

19.9

20.5

20.9

21.8

22.4

 

 

 

 

 

TC

 

249

251

265

289

315

340

361

260

262

272

294

321

344

367

 

 

 

 

85

SHC

 

249

238

226

194

160

130

103

260

254

243

205

167

135

104

 

 

 

 

 

kW

 

21.3

21.3

21.7

22.4

23.1

24.3

24.4

21.6

21.6

22.0

22.5

23.3

23.9

24.6

 

 

 

 

 

TC

 

244

245

257

279

306

328

349

254

256

262

284

310

332

355

 

 

 

 

95

SHC

 

244

230

223

190

156

127

99

254

249

238

201

163

131

100

 

 

 

 

 

kW

 

23.6

23.5

24.1

24.6

25.6

26.2

26.7

23.8

23.9

24.1

24.8

25.5

26.2

26.9

 

 

 

 

 

TC

 

237

238

247

269

293

315

336

246

247

253

274

298

319

343

 

 

 

 

105

SHC

 

237

233

218

185

152

122

95

246

245

233

197

159

127

96

 

 

 

 

 

kW

 

25.9

25.9

26.3

27.0

27.8

28.5

29.2

26.3

26.3

26.5

27.2

28.0

28.7

29.5

 

 

 

 

 

TC

 

229

231

237

258

283

302

322

238

239

243

264

286

306

328

 

 

 

 

115

SHC

 

229

225

213

181

148

119

91

238

239

228

193

155

123

91

 

 

 

 

 

kW

 

28.6

28.6

28.9

29.6

30.3

31.2

31.9

28.9

28.9

29.1

29.7

30.6

31.4

32.1

 

 

 

 

 

TC

 

228

230

236

256

279

299

237

237

241

260

283

304

 

 

 

 

117

SHC

 

228

225

212

180

147

118

237

237

227

192

154

122

 

 

 

 

 

kW

 

29.1

29.1

29.4

30.2

31.0

31.7

29.4

29.5

29.6

30.4

31.2

31.9

 

 

 

 

 

TC

 

226

226

232

252

276

234

234

238

257

280

 

 

 

 

120

SHC

 

226

225

211

179

145

234

234

225

190

152

 

 

 

 

 

kW

 

30.0

30.0

30.3

30.9

31.8

30.3

30.3

30.5

31.1

32.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

579F300 (25 Tons) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

Evaporator Air Quantity — Cfm

 

 

 

 

 

 

 

 

 

Air Entering

 

 

 

 

9,000

 

 

 

 

 

 

10,000

 

 

 

 

300-

 

 

Condenser

 

 

 

 

 

 

Evaporator Air — Ewb (F)/BF

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54/0.53

58/0.37

62/0.18

67/0.15

72/0.14

76/0.17

80/0.00

54/0.57

58/0.41

62/0.23

67/0.16

72/0.15

76/0.17

80/0.00

 

 

 

 

 

 

 

 

579F180

 

 

75

TC

 

277

276

286

310

336

361

385

286

284

291

314

341

365

390

 

 

kW

 

22.2

21.9

22.1

22.7

23.4

24.1

24.8

22.1

22.1

22.2

22.8

23.6

24.2

24.9

 

 

 

 

SHC

 

277

269

261

221

178

142

108

286

284

274

232

186

147

108

 

 

 

 

 

kW

 

19.8

19.5

20.0

20.6

21.3

22.0

22.6

20.0

20.2

20.2

20.8

21.5

22.1

22.7

 

 

 

 

 

TC

 

271

272

277

300

326

349

373

278

278

282

304

330

354

378

 

 

 

 

85

SHC

 

271

264

257

217

175

139

104

278

278

269

228

182

143

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

263

263

268

289

316

337

360

270

270

273

293

319

341

364

 

 

 

 

95

SHC

 

263

263

251

213

171

135

100

270

270

262

223

177

139

101

 

 

 

 

 

kW

 

24.1

24.1

24.3

24.9

25.9

26.4

27.1

24.4

24.4

24.4

25.1

25.8

26.5

27.2

 

 

 

 

 

TC

 

255

255

258

278

302

326

346

261

262

264

282

306

328

352

 

 

 

 

105

SHC

 

255

255

246

208

166

132

96

261

262

254

219

173

135

97

 

 

 

 

 

kW

 

26.5

26.5

26.6

27.3

28.1

29.0

29.6

26.8

26.8

26.9

27.5

28.3

29.0

29.8

 

 

 

 

 

TC

 

247

246

249

267

290

311

253

253

255

270

293

315

 

 

 

 

115

SHC

 

247

246

239

204

162

127

253

253

245

214

168

131

 

 

 

 

 

kW

 

29.1

29.2

29.3

30.0

30.8

31.5

29.3

29.3

29.6

30.1

30.9

31.7

 

 

 

 

 

TC

 

244

244

247

265

288

308

251

251

253

268

291

 

 

 

 

117

SHC

 

244

244

237

203

161

126

251

251

243

213

168

 

 

 

 

 

kW

 

29.7

29.7

29.8

30.4

31.3

32.1

30.0

30.0

30.0

30.6

31.4

 

 

 

 

 

TC

 

241

242

244

261

248

248

250

264

 

 

 

 

120

SHC

 

241

242

235

201

248

248

239

212

 

 

 

 

 

kW

 

30.6

30.6

30.7

31.3

30.8

30.8

31.0

31.5

 

 

LEGEND

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb =

tedb

 

sensible capacity (Btuh)

 

 

1.10 x cfm

 

 

 

tlwb =

Wet-bulb temperature corresponding to enthalpy of air

leaving evaporator coil (hlwb)

 

hlwb =

hewb

total capacity (Btuh)

 

4.5 x cfm

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

FACTOR

81

82

83

84

85

over 85

(BF)

 

 

 

Correction Factor

 

0.05

1.04

2.07

3.11

4.14

5.18

 

0.10

0.98

1.96

2.94

3.92

4.91

 

0.20

0.87

1.74

2.62

3.49

4.36

 

0.30

0.76

1.53

2.29

3.05

3.82

Use formula

0.40

0.65

1.31

1.96

2.62

3.27

shown below.

0.50

0.55

1.09

1.64

2.18

2.73

 

0.60

0.44

0.87

1.31

1.74

2.18

 

0.70

0.33

0.65

0.98

1.31

1.64

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

158

Page 158
Image 158
Bryant 581A/B manual 158

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.