PHYSICAL DATA — 580F180-300 (cont)

UNIT 580F

 

180

210

 

240

300

FURNACE SECTION

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

 

190

190

 

190

190

Burner Orifice Diameter (in. ...drill size)

 

 

 

 

 

 

 

Natural Gas

 

0.1285...30/0.136...29

0.1285...30/0.136...29

 

0.1285...30/0.136...29

0.1285...30/0.136...29

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

 

 

208/230, 575 v

Stage 1

0.98

0.98

 

0.98

0.98

 

460 v

 

Stage 2

0.44

0.44

 

0.44

0.44

 

 

Stage 1

0.80

0.80

 

0.80

0.80

 

Gas Input

Stage 2

0.44

0.44

 

0.44

0.44

 

Stage 1

206,000/270,000

206,000/270,000

 

206,000/270,000

206,000/270,000

Efficiency (Steady-State) (%)

Stage 2

275,000/360,000

275,000/360,000

 

275,000/360,000

275,000/360,000

 

81

81

 

81

81

Temperature Rise Range

 

15-45/20-50

15-45/20-50

 

15-45/20-50

15-45/20-50

Manifold Pressure (in. wg)

 

 

 

 

 

 

 

 

Natural Gas

 

3.3

3.3

 

3.3

3.3

Gas Valve Quantity

 

1

1

 

1

1

Gas Valve Pressure Range

 

 

 

 

 

 

 

 

 

in. wg

 

5.5-13.5

5.5-13.5

 

5.5-13.5

5.5-13.5

 

psig

 

 

0.235-0.487

0.235-0.487

 

0.235-0.487

0.235-0.487

Field Gas Connection Size (in.-FPT)

3/

4

3/

 

3/

4

3/

 

 

 

 

 

4

 

 

4

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

426

 

 

Reset (Auto)

 

 

 

 

320

 

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

Cutout

 

 

 

 

 

27

 

 

Reset (Auto)

 

 

 

 

44

 

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

 

 

Opens

 

 

 

 

30 ± 5

 

 

Closes

 

 

 

 

45 ± 5

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

 

Quantity...Size (in.)

 

 

 

2...20 x 25 x 1

 

 

 

 

 

 

 

 

1...20 x 20 x 1

 

 

RETURN-AIR FILTERS

 

 

 

Throwaway**

 

 

Quantity...Size (in.)

 

 

 

4...20 x 20 x 2

 

 

 

 

 

 

 

 

4...16 x20 x 2

 

 

POWER EXHAUST

 

1/ Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)

 

 

 

 

2

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

Bhp

Brake Horsepower

 

 

 

 

 

 

 

 

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

 

*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils.

†Rollout switch is manual reset.

**The 580F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).

NOTE: The 580F180-300 units have a low-pressure switch (standard) located on the suction side.

OPERATING AND RIGGING WEIGHTS

 

 

 

 

 

BASE UNIT OPERATING WEIGHTS*

 

 

 

UNIT

 

180

 

210

 

240

 

300

 

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

580F

1800

 

816

1850

 

839

1900

 

862

2270

 

1030

*Base unit weight does not include copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information.

NOTE: For 180 or 210 unit, add 75 lb (34 kg) for domestic crating. For 240 unit, add 135 lb (61 kg). For 300 unit, add 175 lb (79 kg) for domestic crating.

OPTIONS AND ACCESSORIES

(Weight Adders)

OPTION/

 

 

 

OPTION/ACCESSORY WEIGHTS

 

 

 

 

180

210

 

 

240

 

300

ACCESSORY

 

 

 

 

 

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

Barometric Relief Damper

50

 

23

50

 

23

50

 

23

50

 

23

Power Exhaust

85

 

39

85

 

39

85

 

39

85

 

39

EconoMi$er IV

90

 

41

90

 

41

90

 

41

90

 

41

Cu Condenser Coil

150

 

68

150

 

68

150

 

68

150

 

68

Cu Condenser and Evaporator Coils

280

 

127

280

 

127

280

 

127

280

 

127

Roof Curb (14-in. curb)

200

 

91

200

 

91

200

 

91

200

 

91

Horizontal Adapter Curb (Pre-Assembled)

250

 

113

250

 

113

250

 

113

250

 

113

Horizontal Adapter Curb (Field-Assembled)

348

 

156

343

 

156

343

 

156

343

 

156

Hail Guard

60

 

27

60

 

27

60

 

27

60

 

27

LEGEND

Cu — Copper

580F180-300

173

Page 173
Image 173
Bryant 581A/B manual 580F180-300

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.