PERFORMANCE DATA (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

2250

513

0.54

505

595

0.76

713

665

1.01

940

728

1.27

1187

786

1.56

1453

 

 

 

2300

521

0.57

531

601

0.79

741

671

1.04

972

734

1.31

1222

791

1.60

1489

 

 

 

2400

535

0.63

584

615

0.86

802

684

1.11

1038

745

1.39

1293

802

1.68

1566

 

 

 

2500

551

0.69

642

628

0.93

866

696

1.19

1109

757

1.47

1369

813

1.77

1647

 

 

 

2550

558

0.72

673

635

0.97

900

702

1.23

1146

763

1.51

1409

818

1.81

1689

 

 

 

2600

566

0.76

705

642

1.00

935

709

1.27

1183

769

1.55

1450

824

1.86

1732

 

 

 

2700

582

0.83

771

656

1.08

1008

721

1.35

1263

781

1.65

1535

835

1.95

1823

 

 

 

2800

597

0.90

842

670

1.16

1086

734

1.44

1347

793

1.74

1625

847

2.06

1917

 

 

 

 

 

 

2900

613

0.98

918

684

1.25

1169

748

1.54

1436

805

1.84

1720

859

2.16

2019

 

 

 

3000

629

1.07

999

699

1.35

1256

761

1.64

1530

818

1.95

1820

871

2.28

2125

 

581B036

 

3400

694

1.47

1374

758

1.78

1660

816

2.10

1961

870

2.44

2275

920

2.79

2603

 

 

3100

645

1.16

1085

713

1.45

1349

775

1.75

1630

831

2.06

1925

883

2.40

2235

 

 

 

3200

662

1.26

1176

728

1.55

1448

788

1.86

1734

844

2.18

2036

895

2.52

2352

 

 

 

3300

678

1.36

1272

743

1.66

1551

802

1.98

1845

857

2.31

2152

908

2.65

2475

 

 

 

3500

711

1.59

1482

773

1.90

1775

831

2.23

2082

884

2.58

2402

933

2.93

2737

 

-150

 

3600

727

1.71

1596

789

2.03

1896

845

2.37

2210

897

2.72

2537

946

3.09

2877

 

 

3700

744

1.84

1716

804

2.17

2023

860

2.51

2343

911

2.87

2677

959

3.24

3023

 

 

 

3750

752

1.91

1778

812

2.24

2089

867

2.59

2413

918

2.95

2750

966

3.32

3100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581B090 (71/2 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

2250

839

1.86

1735

889

2.18

2032

935

2.52

2345

980

2.87

2673

1022

3.23

3015

 

 

 

2300

844

1.90

1773

893

2.22

2073

940

2.56

2389

984

2.91

2718

1027

3.28

3062

 

 

 

2400

854

1.99

1855

903

2.32

2159

950

2.66

2478

993

3.02

2812

1035

3.39

3159

 

 

 

2500

865

2.08

1940

913

2.41

2249

959

2.76

2573

1003

3.12

2911

1044

3.50

3261

 

 

 

2550

870

2.13

1985

918

2.46

2296

964

2.81

2622

1008

3.18

2962

1049

3.55

3315

 

 

 

2600

875

2.18

2031

923

2.51

2344

969

2.87

2673

1012

3.23

3014

1054

3.61

3370

 

 

 

2700

886

2.28

2126

934

2.62

2445

979

2.98

2777

1022

3.35

3123

1063

3.74

3483

 

 

 

2800

897

2.39

2227

944

2.73

2550

989

3.10

2888

1032

3.47

3238

1073

3.86

3601

 

 

 

2900

908

2.50

2333

955

2.85

2661

1000

3.22

3003

1042

3.60

3358

1083

4.00

3725

 

 

 

3000

920

2.62

2443

966

2.98

2777

1010

3.35

3123

1052

3.74

3484

1093

4.14

3856

 

 

 

3100

931

2.75

2560

977

3.11

2899

1021

3.49

3250

1063

3.88

3615

 

 

 

3200

943

2.88

2682

989

3.25

3026

1032

3.63

3383

1074

4.02

3752

 

 

 

3300

955

3.01

2810

1000

3.39

3159

1043

3.78

3521

1084

4.18

3896

 

 

 

3400

967

3.16

2945

1012

3.54

3299

1055

3.93

3667

 

 

 

3500

980

3.31

3084

1024

3.69

3445

1066

4.09

3817

 

 

 

3600

992

3.46

3230

1036

3.86

3596

 

 

 

3700

1005

3.63

3383

1048

4.03

3755

 

 

 

3750

1011

3.71

3462

1054

4.11

3836

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.

Refer to page 103 for general Fan Performance Data notes.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 4.20.

109

Page 109
Image 109
Bryant 581A/B manual 581B090 71/2 Tons HIGH-STATIC Motor Belt Drive

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.