PERFORMANCE DATA (cont)

a50-4028

Fan Performance Using Accessory

Power Exhaust (581A155,180)

ALTITUDE COMPENSATION* — 581A155,180

(Natural Gas Units)

ELEVATION

NATURAL GAS ORIFICE SIZE†

(ft)

Low Heat

High Heat

0-3,000

30

29

3,000-

7,000

31

30

7,000-

9,000

32

31

9,000-10,000

33

31

above 10,000

35

32

ALTITUDE COMPENSATION — 581A210-300

(LP Gas)

ELEVATION

 

ORIFICE SIZE — LP GAS

 

(ft)

Low

Medium

High Heat

High Heat

Heat

Heat

(6 Cell)

(8 Cell)

 

0-2,000

35

38

35

35

2,000

36

39

36

36

3,000

36

39

36

36

4,000

37

40

37

37

5,000

37

40

37

37

6,000

38

41

38

38

7,000

39

42

39

39

8,000

40

43

40

40

9,000

41

44

41

41

above 10,000

42

45

42

42

ALTITUDE DERATING FACTOR*

ELEVATION

MAXIMUM HEATING VALUE

(ft)

(Btu/ft3)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

*Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant dealer.

IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.

ALTITUDE COMPENSATION — 581A155,180

(LP Gas Units)

ELEVATION

LIQUID PROPANE ORIFICE SIZE

(ft)

Low Heat and High Heat

0-2,000

36

2,000

37

3,000

38

4,000

38

5,000

39

6,000

40

7,000

41

8,000

41

9,000

42

10,000

43

EVAPORATOR-FAN MOTOR EFFICIENCY —

581A155,180

MOTOR

MOTOR EFFICIENCY

HORSEPOWER

(%)

3.0

81.7

2.9, 3.7

85.8

5.0

87.5

NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.

ALTITUDE COMPENSATION — 581A210-300

(Natural Gas)

 

 

 

 

ELEVATION

 

ORIFICE SIZE — NATURAL GAS

 

300

 

 

(ft)

Low

 

Medium

High Heat

High Heat

 

 

 

Heat

 

Heat

(6 Cell)

(8 Cell)

 

 

 

 

 

 

 

 

 

 

 

 

581A155-

 

 

0-2,000

29

 

30

29

29

 

 

2,000

29

 

30

29

29

 

 

 

 

 

 

 

 

 

3,000

30

 

31

30

30

 

 

 

 

4,000

30

 

31

30

30

 

 

 

 

5,000

30

 

31

30

30

 

 

 

 

6,000

30

 

31

30

30

 

 

 

 

7,000

31

 

32

31

31

 

 

 

 

 

 

 

 

 

8,000

31

 

32

31

31

 

 

 

 

9,000

31

 

32

31

31

 

 

 

 

above 10,000

32

 

33

32

32

240

Page 240
Image 240
Bryant 581A/B Altitude COMPENSATION* 581A155,180, Altitude Compensation 581A210-300, Altitude Compensation 581A155,180

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.