PERFORMANCE DATA — 579F (cont)

Fan Performance Using Accessory Power Exhaust (579F180-300)

ALTITUDE COMPENSATION* —

579F180-300

ELEVATION

NATURAL GAS ORIFICE SIZE†

(ft)

Low Heat

High Heat

0-3,000

30

29

3,000-

7,000

31

30

7,000-

9,000

32

31

9,000-10,000

33

31

above 10,000

35

32

*Includes a 4% input reduction per each 1,000 feet. †Orifices available through your Bryant distributor.

ALTITUDE DERATING FACTOR*

ELEVATION (ft)

MAXIMUM HEATING VALUE

(Btu/ft3)

 

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, then changing spuds may not be required.