Bryant 581A/B FAN Performance Vertical Discharge Units, 580F048 4 Tons Alternate Motor Belt Drive

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 38
Image 38

580F036-151

PERFORMANCE DATA (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

580F048 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

Low Speed

 

 

 

 

 

 

High Speed

 

 

 

 

 

 

208 V

 

 

230, 460, 575 V

 

 

208 V

 

 

230, 460, 575 V

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

ESP

Bhp

 

Watts

ESP

 

Bhp

 

Watts

ESP

Bhp

Watts

ESP

 

Bhp

 

Watts

 

1200

 

0.68

0.41

 

458

0.74

 

0.45

 

506

0.74

0.51

572

0.85

 

0.56

 

632

 

1300

 

0.61

0.42

 

471

0.67

 

0.46

 

521

0.66

0.52

589

0.78

 

0.58

 

651

 

1400

 

0.53

0.45

 

503

0.59

 

0.49

 

556

0.59

0.54

616

0.70

 

0.60

 

681

 

1500

 

0.45

0.47

 

536

0.51

 

0.52

 

593

0.52

0.56

631

0.63

 

0.62

 

698

 

1600

 

0.36

0.49

 

557

0.42

 

0.54

 

616

0.45

0.58

654

0.56

 

0.64

 

723

 

1700

 

0.26

0.52

 

584

0.32

 

0.57

 

646

0.37

0.60

678

0.48

 

0.66

 

750

 

1800

 

0.15

0.54

 

610

0.22

 

0.60

 

674

0.30

0.62

698

0.41

 

0.68

 

772

 

1900

 

0.04

0.56

 

629

0.11

 

0.62

 

696

0.23

0.64

720

0.34

 

0.70

 

796

 

2000

 

 

 

 

0.16

0.66

744

0.26

 

0.73

 

823

 

 

LEGEND

 

 

 

 

 

 

 

See page 70 for general fan performance notes.

 

 

 

 

Bhp

Brake Horsepower Input to Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)*

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

(Cfm)

 

 

0.2

 

 

0.4

 

 

 

 

0.6

 

 

 

0.8

 

 

 

1.0

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

1200

 

666

0.26

257

778

0.37

 

367

 

871

0.47

471

 

952

0.57

572

 

1025

0.67

670

1300

 

701

0.31

306

810

0.43

 

426

 

901

0.54

540

 

981

0.65

651

 

1053

0.76

760

1400

 

737

0.36

361

842

0.49

 

491

 

931

0.62

616

 

1010

0.74

738

 

1081

0.86

856

1500

 

773

0.42

422

875

0.57

 

564

 

963

0.70

699

 

1040

0.84

831

 

1110

0.96

960

1600

 

810

0.49

491

909

0.65

 

643

 

994

0.79

790

 

1070

0.94

932

 

1140

1.08

1070

1700

 

847

0.57

567

943

0.73

 

730

 

1027

0.89

888

 

1101

1.05

1040

 

1170

1.20

1189

1800

 

885

0.66

652

978

0.83

 

826

 

1060

1.00

994

 

1133

1.16

1157

 

1900

 

923

0.75

745

1014

0.94

 

930

 

1093

1.11

1109

 

 

2000

 

962

0.85

847

1049

1.05

 

1043

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580F048 (4 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

 

1.6

 

 

 

1.8

 

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

1200

 

1093

0.77

767

1155

0.87

 

861

 

1213

0.96

955

 

1268

1.05

1047

 

1321

1.14

1137

1300

 

1119

0.87

866

1181

0.98

 

970

 

1239

1.08

1073

 

1294

1.18

1175

 

1400

 

1147

0.98

972

1208

1.09

 

1086

 

 

 

1500

 

1175

1.09

1086

 

 

 

 

1600

 

 

 

 

 

1700

 

 

 

 

 

1800

 

 

 

 

 

1900

 

 

 

 

 

2000

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

Bhp —

Brake Horsepower Input to Fan

 

 

 

 

 

 

1. Boldface indicates field-supplied drive is required.

 

 

 

 

 

 

 

 

2. Maximum continuous bhp is 1.20.

 

 

 

 

 

Watts —

Input Watts to Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. See page 70 for general fan performance notes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Motor drive range: 770 to 1175 rpm. All other rpms require a field-supplied drive.

580F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.2

 

 

0.4

 

 

 

 

0.6

 

 

 

0.8

 

 

1.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

666

0.26

257

778

0.37

 

367

 

871

0.47

471

 

952

0.57

572

1025

0.67

670

1300

701

0.31

306

810

0.43

 

426

 

901

0.54

540

 

981

0.65

651

1053

0.76

760

1400

737

0.36

361

842

0.49

 

491

 

931

0.62

616

 

1010

0.74

738

1081

0.86

856

1500

773

0.42

422

875

0.57

 

564

 

963

0.70

699

 

1040

0.84

831

1110

0.96

960

1600

810

0.49

491

909

0.65

 

643

 

994

0.79

790

 

1070

0.94

932

1140

1.08

1070

1700

847

0.57

567

943

0.73

 

730

 

1027

0.89

888

 

1101

1.05

1040

1170

1.20

1189

1800

885

0.66

652

978

0.83

 

826

 

1060

1.00

994

 

1133

1.16

1157

1200

1.32

1316

1900

923

0.75

745

1014

0.94

 

930

 

1093

1.11

1109

 

1165

1.29

1283

1231

1.46

1453

2000

962

0.85

847

1049

1.05

 

1043

 

1127

1.24

1233

 

1198

1.42

1417

1263

1.61

1598

 

 

 

 

 

 

 

 

 

 

 

 

 

580F048 (4 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

1.2

 

 

1.4

 

 

 

 

1.6

 

 

 

1.8

 

 

2.0

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

 

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

1093

0.77

767

1155

0.87

 

861

 

1213

0.96

955

 

1268

1.05

1047

1321

1.14

1137

1300

1119

0.87

866

1181

0.98

 

970

 

1239

1.08

1073

 

1294

1.18

1175

1346

1.28

1275

1400

1147

0.98

972

1208

1.09

 

1086

 

1265

1.21

1199

 

1320

1.32

1310

1371

1.43

1419

1500

1175

1.09

1086

1235

1.22

 

1209

 

1292

1.34

1332

 

1346

1.46

1452

1397

1.58

1572

1600

1204

1.21

1207

1263

1.35

 

1340

 

1320

1.48

1472

 

1373

1.61

1603

1424

1.74

1732

1700

1233

1.34

1336

1292

1.49

 

1480

 

1348

1.63

1622

 

1401

1.77

1762

1451

1.91

1901

1800

1262

1.48

1473

1321

1.64

 

1627

 

1376

1.79

1779

 

1428

1.94

1930

1479

2.09

2078

1900

1293

1.63

1620

1350

1.79

 

1784

 

1405

1.96

1946

 

1457

2.12

2106

1506

2.28

2265

2000

1323

1.79

1776

1380

1.96

 

1950

 

1434

2.13

2123

 

1486

2.31

2293

 

 

LEGEND

Bhp

Brake Horsepower Input to Fan

Watts

Input Watts to Motor

*Motor drive range: 1075 to 1455 rpm. All other rpms require a field-supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

3.See page 70 for general fan performance notes.

38

Page 38
Image 38
Bryant 581A/B manual FAN Performance Vertical Discharge Units, 580F048 4 Tons Standard Motor Direct Drive

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.