Bryant 581A/B 579F180-300, Operating and Rigging Weights, Options and Accessories, Weight Adders

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 145
Image 145

PHYSICAL DATA — 579F180-300 (cont)

 

UNIT 579F

 

180

216

240

300

FURNACE SECTION

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

190

190

190

190

Burner Orifice Diameter (in. ...drill size)

 

 

 

 

 

 

Natural Gas

 

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

208/230, 575

Stage 1

0.98

0.98

0.98

0.98

 

 

Stage 2

0.44

0.44

0.44

0.44

 

460 v

Stage 1

0.80

0.80

0.80

0.80

 

 

Stage 2

0.44

0.44

0.44

0.44

Gas Input

Stage 1

172,000/225,000

206,000/270,000

206,000/270,000

206,000/270,000

Efficiency (Steady State) (%)

Stage 2

230,000/300,000

275,000/360,000

275,000/360,000

275,000/360,000

 

81

81

81

81

Temperature Rise Range

 

15-45/20-50

15-45/20-50

15-45/20-50

15-45/20-50

Manifold Pressure (in. wg)

 

 

 

 

 

 

 

Natural Gas

 

3.3

3.3

3.3

3.3

Gas Valve Quantity

 

1

1

1

1

Field Gas Connection Size (in.-FPT)

3/

3/

4

3/

3/

 

 

 

4

 

4

4

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

Cutout

 

 

 

426

 

Reset (Auto)

 

 

 

320

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

Cutout

 

 

 

27

 

Reset (Auto)

 

 

 

44

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

Opens

 

 

 

30 ± 5

 

Closes

 

 

 

45

± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

Quantity...Size (in.)

 

 

 

2...20 x 25 x 1

 

 

 

 

 

 

1...20 x 20 x 1

 

RETURN-AIR FILTERS

 

 

 

Throwaway**

 

Quantity...Size (in.)

 

 

 

4...20 x 20 x 2

 

 

 

 

 

 

4...16 x 20 x 2

 

POWER EXHAUST

 

1/ Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)

 

 

 

2

 

 

 

 

 

LEGEND

 

 

†Rollout switch is manual reset.

 

Bhp

Brake Horsepower

 

 

**The 579F300 units requires 2-in. industrial-grade filters capable of handling face

 

 

velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).

TXV

Thermostatic Expansion Valve

 

 

 

 

 

 

NOTE: The 579F units have a low-pressure switch (standard) located on the suc-

*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora- tion side. tor coils; and Circuit 2 uses the upper portion of both coils.

OPERATING AND RIGGING WEIGHTS

 

 

 

 

BASE UNIT OPERATING WEIGHTS*

 

 

 

 

UNIT

 

180

216

 

240

 

 

300

 

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

579F

1650

 

748

1800

 

816

1850

 

839

2000

 

907

*Base unit weight does not include electric heaters, copper coils, economizer,

NOTE: For 180 and 216 unit sizes add 75 lb (34 kg) for domestic crating. For 240

power exhaust, barometric relief or crating. See Options and Accessories table

and 300 unit sizes add 135 lb (61 kg). For export crating add 500 lb (227 kg).

below for more information.

 

 

 

 

 

 

 

 

 

 

 

 

579F180-300

OPTIONS AND ACCESSORIES

(Weight Adders)

OPTION/

 

 

 

 

OPTION/ACCESSORY WEIGHTS

 

 

 

 

180

 

216

 

240

 

300

ACCESSORY

 

 

 

 

 

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

Barometric Relief Damper

50

 

23

50

 

23

50

 

23

50

 

23

Power Exhaust

85

 

39

85

 

39

85

 

39

85

 

39

EconoMi$er IV

90

 

41

90

 

41

90

 

41

90

 

41

Cu Condenser Coil

150

 

68

150

 

68

150

 

68

150

 

68

Cu Condenser and Evaporator Coils

280

 

127

280

 

127

280

 

127

280

 

127

Roof Curb (14-in. curb)

200

 

91

200

 

91

200

 

91

200

 

91

Horizontal Adapter Curb (Pre-Assembled)

250

 

113

250

 

113

250

 

113

250

 

113

Horizontal Adapter Curb (Field-Assembled)

343

 

156

343

 

156

343

 

156

343

 

156

Hail Guard

60

 

27

60

 

27

60

 

27

60

 

27

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

Cu — Copper

145

Page 145
Image 145
Bryant 581A/B manual 579F180-300, Operating and Rigging Weights, Options and Accessories, Weight Adders

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.