Bryant 581A/B manual Outdoor Sound Power Total Unit, Unit Sound Octave Bands Rating, Component CFM

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 128
Image 128
watts =

PERFORMANCE DATA (cont)

OUTDOOR SOUND POWER (TOTAL UNIT)

UNIT

SOUND

 

 

 

OCTAVE BANDS

 

 

 

RATING

 

 

 

 

 

 

 

 

581B

63

125

250

500

1000

2000

4000

8000

(dB)

036,048

76

55.9

66.0

64.0

66.2

68.4

64.5

61.7

57.3

060,072

80

59.1

68.9

68.7

71.9

74.0

68.9

65.7

59.0

090,102

82

62.2

69.3

71.5

74.7

76.2

72.9

68.7

61.5

120

84

64.6

71.1

73.3

76.9

77.6

73.7

70.6

63.7

150

86

63.7

69.9

72.5

78.2

81.1

77.3

73.3

66.8

LEGEND

NOTE: The indoor sound power is available in Bryant’s Electronic Catalog

dB — Sound Levels (decibels)

program (ECAT) for specific operating parameters.

 

581B036-150

EVAPORATOR-FAN MOTOR EFFICIENCY

UNIT SIZE 581B

EFFICIENCY%

036,048

75

060

74/84*

072

84

090,102

80

120

85

150

87

*Single phase/3 phase.

NOTES:

1. Convert bhp to watts using the following formula: bhp (746)

motor efficiency

2.The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regulated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT-compliant energy-efficient motor. Variable-speed motors are exempt from EPACT compliance require- ments. Therefore, the indoor fan motors for Bryant 581B036-150 units are exempt from these requirements.

ACCESSORY/FIOP ECONOMI$ER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 581B036-072

COMPONENT

 

 

 

 

CFM

 

 

 

 

1250

1500

1750

2000

 

2250

2500

2750

 

3000

 

 

 

Vertical EconoMi$er IV and EconoMi$er2

0.045

0.065

0.08

0.12

 

0.145

0.175

0.22

 

0.255

Horizontal EconoMi$er IV and EconoMi$er2

0.1

0.125

 

0.15

0.18

0.225

 

0.275

LEGEND

 

 

*The static pressure must be added to external static pressure. The sum and

FIOP — Factory-Installed Option

 

 

the evaporator entering-air cfm should be used in conjunction with the Fan

 

 

Performance tables to determine indoor blower rpm and watts.

 

 

 

 

 

ACCESSORY/FIOP ECONOMI$ER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 581B090-150

COMPONENT

 

 

 

 

 

 

CFM

 

 

 

 

 

 

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

 

Vertical EconoMi$er IV and

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

EconoMi$er2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal EconoMi$er IV and

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

EconoMi$er2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

*The static pressure must be added to external static pressure. The sum and

FIOP — Factory-Installed Option

 

 

 

 

 

the evaporator entering-air cfm should be used in conjunction with the Fan

 

 

 

 

 

Performance tables to determine indoor blower rpm and watts.

 

 

 

 

 

 

 

 

128

Page 128
Image 128
Bryant 581A/B Outdoor Sound Power Total Unit, Unit Sound Octave Bands Rating, Unit Size 581B EFFICIENCY%, Component CFM

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.