GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)

M. Special Features:

o. Compressor lockout sensor (opens at 35 F,

Certain features are not applicable when the features

closes at 50 F).

p. Actuator shall be direct coupled to economizer

designated * are specified. For assistance in amending

the specifications, contact your local Bryant Sales Office.

gear, eliminating linkage arms and rods.

1. Full Perimeter Roof Curbs (Horizontal and Vertical):

q. Control LEDs:

a.Formed of 14-gage galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.

b.Permits installing and securing ductwork to curb prior to mounting unit on the curb.

c.Retrofit roof curb kit shall be available for fit up to existing Bryant roof curbs.

*2. Integrated Economizer:

a. Integrated integral modulating type capable of simultaneous economizer and compressor operation.

b. Available as a factory-installed option in vertical supply/return configuration only. (Available as a field-installed accessory for dedicated horizontal and/or vertical supply return configurations.)

c. Includes all hardware and controls to provide cooling with outdoor air.

d. Equipped with low-leakage dampers, not to exceed 2% leakage at 1 in. wg pressure differential.

e.Capable of introducing up to 100% outdoor air.

f.EconoMi$er IV shall be equipped with a baromet- ric relief damper.

g.Designed to close damper(s) during loss-of- power situations with spring return built into motor.

h.Dry bulb outdoor-air temperature sensor shall be provided as standard. Outdoor air sensor set point is adjustable and shall range from 40 to 100 F. For the EconoMi$er IV, the return air sen- sor, indoor enthalpy sensor, and outdoor enthalpy sensor shall be provided as field-installed acces- sories to provide enthalpy control, differential enthalpy control, and differential dry bulb temper- ature control.

i.EconoMi$er IV controller shall use a mixed air thermistor mounted on the evaporator fan hous- ing to control EconoMi$er IV operation to a supply air temperature of 55 F.

j.The EconoMi$er IV shall have a gear-driven par- allel blade design.

k.EconoMi$er IV controller shall provide control of internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%.

l.EconoMi$er IV controller Occupied Minimum Damper Position Setting maintains the minimum airflow into the building during occupied period providing design ventilation rate for full occupancy (damper position during heating). A remote potentiometer may be used to override the set point.

m.EconoMi$er IV controller Unoccupied Minimum Damper Position Setting — The EconoMi$er IV dampers shall be completely closed when the unit is in the occupied mode.

n.EconoMi$er IV controller IAQ/DCV control modu- lates the outdoor-air damper to provide ventilation

based on the optional 2 to 10 vdc CO2 sensor input.

1)When the outdoor air damper is capable of providing free cooling, the “Free Cool” LED shall illuminate.

2)The IAQ LED indicates when the module is on the DCV mode.

3)The EXH LED indicates when the exhaust fan contact is closed.

r.Remote Minimum Position Control — A field- installed accessory remote potentiometer allows the outdoor air damper to be opened or closed beyond the minimum position in the occupied mode for modified ventilation.

*3. Barometric Relief Damper Package:

a.Package shall include damper, seals, hardware, and hoods to relieve excess internal pressure.

b.Damper shall close due to gravity upon unit shutdown.

*4. Power Exhaust:

Package shall include an exhaust (centrifugal style) fan, 1 Hp 208-230, 460 v (factory-wired for 460 v) direct-drive motor, and damper for vertical flow units with economizer to control over-pressurization of building.

*5. Thermostats and Subbases:

Units shall provide staged heating and cooling in addition to automatic (or manual) changeover and fan control.

*6. Electronic Programmable Thermostat:

Thermostat shall be capable of using deluxe full- featured electronic thermostat.

7. Liquefied Propane Conversion Kit:

Kit shall contain all the necessary hardware and instructions to convert a standard natural gas unit for use with liquefied propane gas.

8. Convenience Outlet:

Outlet shall be factory-installed and internally mounted with an externally accessible 115-v, 15 amp GFI, female receptacle with hinged cover. A step down transformer shall be included so no additional wiring is necessary.

9. Non-Fused Disconnect Switch:

Switch shall be factory-installed, internally mounted, NEC and UL approved. Non-fused switch shall pro- vide unit power shutoff. Shall be accessible from out- side the unit and shall provide power off lockout capability.

10. Hail Guard, Condenser Coil Grille:

Grille shall protect the condenser coil from hail, flying debris, and damage by large objects without increas- ing unit clearances.

11. Horizontal Kit:

Horizontal kit shall contain all the necessary hard- ware to convert a vertical airflow unit to a horizontal airflow unit.

The unit shall also be available as a horizontal air- flow unit directly from the factory.

581A210-300

257

Page 257
Image 257
Bryant 581A/B manual 257

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.