Bryant 581A/B manual General Notes for FAN Performance Data Tables, Outdoor Sound Power Total Unit

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 70
Image 70

580F036-151

PERFORMANCE DATA (cont)

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1.

Values include losses for filters, unit casing, and wet coils. See this

 

affected. See Evaporator-Fan Motor Performance table on page 73

 

page for accessory/FIOP static pressure information.

 

for additional information.

2.

Extensive motor and electrical testing on these units ensures that

3.

Use of a field-supplied motor may affect wire sizing. Contact your

 

the full range of the motor can be utilized with confidence. Using fan

 

Bryant representative for details.

 

motors up to the wattage ratings shown will not result in nuisance

4.

Interpolation is permissible. Do not extrapolate. (Belt drive units

 

tripping or premature motor failure. Unit warranty will not be

 

only.)

OUTDOOR SOUND POWER (Total Unit)

 

SOUND

A-WEIGHTED

 

 

 

OCTAVE BANDS

 

 

 

UNIT 580F

RATING

 

 

 

 

 

 

 

 

(dB)

63

125

250

500

1000

2000

4000

8000

 

60 Hz (dB)

 

 

 

 

 

 

 

 

 

 

036-072

81

80.5

56.8

75.8

72.4

72.9

74.8

75.4

71.3

69.1

073

80

80.0

59.1

68.9

68.7

71.9

74.0

68.9

65.7

59.0

090

87

86.4

83.2

87.4

83.5

82.8

83.0

77.7

71.8

67.0

091, 103

82

82.0

62.2

69.3

71.5

74.7

76.2

72.9

68.7

61.5

120

88

87.6

97.6

90.4

85.7

84.8

83.9

77.5

71.3

65.8

121

84

84.0

64.6

71.7

73.3

76.9

77.6

73.7

70.6

63.7

150

87

86.4

83.7

87.2

83.4

82.8

83.0

77.7

71.8

67.0

151

86

86.0

63.7

69.9

72.5

78.2

81.1

77.3

73.3

66.8

NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters.

ACCESSORY/FIOP ECONOMIZER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F036-073

COMPONENT

 

 

 

 

CFM

 

 

 

1250

1500

1750

2000

 

2250

2500

2750

3000

 

 

Vertical EconoMi$er IV and EconoMi$er2

0.045

0.065

0.08

0.12

 

0.145

0.175

0.22

0.255

Horizontal EconoMi$er IV and EconoMi$er2

0.1

0.125

 

0.15

0.18

0.225

0.275

LEGEND

 

 

*The static pressure must be added to external static pressure. The

FIOP — Factory-Installed Option

 

 

sum and the evaporator entering-air cfm should be used in conjunction

 

 

with the Fan Performance tables to determine indoor blower rpm and

 

 

 

watts.

ACCESSORY/FIOP ECONOMISER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F090-151

COMPONENT

 

 

 

 

 

 

CFM

 

 

 

 

 

 

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

 

Vertical EconoMi$er IV

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

and EconoMi$er2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal EconoMi$er IV

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

and EconoMi$er2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in con- junction with the Fan Performance tables to determine blower rpm and watts.

70

Page 70
Image 70
Bryant 581A/B manual General Notes for FAN Performance Data Tables, Outdoor Sound Power Total Unit, Component CFM