PERFORMANCE DATA — 579F (cont)

 

 

 

 

 

 

 

COOLING CAPACITIES (cont)

 

 

 

 

 

 

 

 

 

 

579F216 (18 Tons) (cont)

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

Evaporator Air Quantity — Cfm

 

 

 

 

 

 

 

9000

 

 

 

 

 

Air Entering

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

Evaporator Air — Ewb (F)/BF

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

54/0.65

58/0.53

 

62/0.40

67/0.25

72/0.23

 

76/0.23

80/0.05

 

 

 

 

 

 

 

TC

223

223

 

228

239

258

 

275

 

75

SHC

223

223

 

202

181

144

 

113

 

 

kW

14.3

14.3

 

14.4

14.6

15.0

 

15.4

 

 

TC

216

217

 

222

231

250

 

266

 

85

SHC

216

217

 

194

177

141

 

110

 

 

kW

15.8

15.9

 

16.0

16.3

16.7

 

17.1

 

 

TC

210

210

 

215

223

241

 

257

 

95

SHC

210

210

 

187

174

138

 

107

 

 

kW

17.6

17.6

 

17.7

18.0

18.4

 

18.8

 

 

TC

202

202

 

207

214

231

 

 

105

SHC

202

202

 

184

170

134

 

 

 

kW

19.4

19.4

 

19.5

19.7

20.2

 

 

 

TC

195

195

 

196

204

221

 

 

115

SHC

195

195

 

192

166

131

 

 

 

kW

21.3

21.3

 

21.4

21.7

22.2

 

 

 

TC

193

193

 

194

202

219

 

 

117

SHC

193

193

 

192

166

130

 

 

 

kW

21.7

21.7

 

21.7

22.0

22.6

 

 

 

TC

191

191

 

191

199

 

 

120

SHC

191

191

 

191

164

 

 

 

kW

22.3

22.3

 

22.3

22.6

 

 

 

 

LEGEND

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

BF

Bypass Factor

 

Below 80 F edb, subtract (corr factor x cfm) from SHC.

 

 

Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

Edb

Entering Dry-Bulb

 

 

 

 

 

 

 

 

 

 

 

Ewb

Entering Wet-Bulb

 

 

 

ENTERING AIR DRY-BULB TEMP (F)

kW

Compressor Motor Power Input

 

BYPASS

 

ldb

Leaving Dry-Bulb

 

79

78

77

76

75

under 75

lwb

Leaving Wet-Bulb

 

FACTOR

 

 

 

 

 

 

 

81

82

83

84

85

over 85

 

(BF)

SHC

Sensible Heat Capacity (1000 Btuh) Gross

 

 

 

 

 

Correction Factor

 

TC

Total Capacity (1000 Btuh) Gross

 

 

 

 

 

NOTES:

 

 

 

 

 

 

0.05

1.04

2.07

3.11

4.14

5.18

 

 

 

 

 

 

 

0.10

0.98

1.96

2.94

3.92

4.91

 

1.

Direct interpolation is permissible. Do not extrapolate.

 

 

2.

The following formulas may be used:

 

0.20

0.87

1.74

2.62

3.49

4.36

 

 

tldb =

tedb

 

sensible capacity (Btuh)

 

 

0.30

0.76

1.53

2.29

3.05

3.82

Use formula

 

 

1.10 x cfm

 

0.40

0.65

1.31

1.96

2.62

3.27

shown below.

 

 

 

 

 

 

 

 

 

 

 

 

 

0.50

0.55

1.09

1.64

2.18

2.73

 

 

tlwb =

Wet-bulb temperature corresponding to enthalpy of air

 

0.60

0.44

0.87

1.31

1.74

2.18

 

 

leaving evaporator coil (hlwb)

 

0.70

0.33

0.65

0.98

1.31

1.64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hlwb =

hewb

total capacity (Btuh)

 

 

Interpolation is permissible.

 

 

 

 

 

4.5 x cfm

 

 

 

 

 

 

 

 

 

 

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

 

 

 

 

 

 

 

 

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil

579F180-300

155

Page 155
Image 155
Bryant 581A/B manual 155

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.