Bryant 581A/B manual Unit Size Nominal IFM Voltage Range

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 77
Image 77

ELECTRICAL DATA (cont)

UNIT SIZE

NOMINAL

IFM

NO

VOLTAGE RANGE

COMPRESSOR (each)

OFM (each)

IFM

COMBUSTION

49.1

60

MINIMUM UNIT

580F036-

 

52

316

CONV

FAN MOTOR

POWER SUPPLY

DISCONNECT SIZE*

 

580F

V-PH-Hz

TYPE

OUTLET

Min

Max

Qty

RLA

LRA

Qty

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

 

 

 

STD

NO

 

 

 

 

 

 

 

5.8

 

44.3

50

46

272

 

 

208/230-3-60

YES

187

254

2

17.3

120.0

2

1.4

0.6

49.1

60

52

277

 

 

 

 

 

 

HIGH

 

10.6

 

 

 

 

151

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

21.0

25

22

149

 

 

 

YES

 

 

 

 

 

 

 

 

 

53.9

60

57

320

 

 

 

STD

 

 

 

 

 

 

 

 

2.6

 

 

 

 

 

 

103

460-3-60

YES

414

508

2

7.9

70.0

2

0.7

0.3

23.2

30

24

151

 

 

 

 

(81/2 Ton)

HIGH

NO

4.8

23.2

30

24

171

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

25.4

30

27

173

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

2.0

 

16.7

20

17

109

 

 

575-3-60

YES

518

632

2

5.5

50.0

2

0.6

0.3

18.4

25

19

111

 

 

 

 

 

 

HIGH

NO

2.8

18.5

25

19

126

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

20.2

25

21

128

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

5.8

 

44.2

50

46

307

 

 

 

YES

 

 

 

 

 

 

 

 

50.2

60

52

311

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

ALT

NO

187

254

2

15.8

130

2

1.4

7.5

0.6

45.9

50

48

326

 

 

YES

51.9

60

54

330

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

15.0

 

53.4

60

57

374

 

 

 

YES

 

 

 

 

 

 

 

 

59.4

70

62

378

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

2.6

 

21.8

25

23

152

 

 

 

YES

 

 

 

 

 

 

 

 

27.8

30

25

154

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

460-3-60

ALT

NO

414

508

2

7.9

64

2

0.7

3.4

0.3

22.6

25

24

191

 

(10 Ton)

YES

25.3

30

26

193

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

7.4

 

26.6

30

28

185

 

 

 

YES

 

 

 

 

 

 

 

 

29.3

35

31

187

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

2.0

 

18.1

25

19

123

 

 

 

YES

 

 

 

 

 

 

 

 

24.1

25

21

109

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

ALT

NO

518

632

2

6.6

52

2

0.6

2.0

0.3

18.7

25

20

155

 

 

YES

24.7

25

22

141

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

2.8

 

21.9

30

23

150

 

 

 

YES

 

 

 

 

 

 

 

 

24.6

30

25

136

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

5.8

 

44.6

50

46

307

 

 

 

YES

 

 

 

 

 

 

 

 

49.4

60

52

312

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

ALT

NO

187

254

2

15.8

130

2

1.4

7.5

0.6

46.3

60

48

326

 

 

YES

51.1

60

54

331

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

15.0

 

53.8

60

57

374

 

 

 

YES

 

 

 

 

 

 

 

 

58.6

70

62

379

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

2.6

 

22.0

25

23

152

 

 

 

YES

 

 

 

 

 

 

 

 

24.2

30

25

154

 

 

 

 

 

 

 

 

 

 

 

 

 

 

121

460-3-60

ALT

NO

414

508

2

7.9

64

2

0.7

3.4

0.3

22.8

25

24

191

 

(10 Ton)

YES

25.0

30

26

193

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

7.4

 

26.8

30

28

185

 

 

 

YES

 

 

 

 

 

 

 

 

29.0

35

30

187

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

NO

 

 

 

 

 

 

 

2.0

 

18.1

20

19

123

 

 

 

YES

 

 

 

 

 

 

 

 

19.8

25

21

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

ALT

NO

518

632

2

6.6

52

2

0.6

2.8

0.3

18.7

20

20

150

 

 

YES

20.4

25

22

156

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH

NO

 

 

 

 

 

 

 

3.3

 

21.9

25

23

155

 

 

 

YES

 

 

 

 

 

 

 

 

23.6

25

25

151

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Determine percent of voltage imbalance.

FLA — Full Load Amps

% Voltage Imbalance = 100 x

7

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect per NEC. †Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

3.For units with power exhaust: If a single power source is to be used, size wire to include power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the power exhaust using the following formula:

MCA New = MCA unit only + MCA of Power Exhaust

For example, using a 580F060 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A01 power exhaust.

MCA New = 28.9 amps + 1.6 amps = 30.5 amps

If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New is below 35, therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC.

POWER EXHAUST ELECTRICAL DATA

 

 

 

 

 

MOCP

POWER EXHAUST

APPLICATION

MCA

MCA

MCA

(separate

PART NO.

USAGE

(230 V)

(460 V)

(575 V)

power source

 

 

 

 

 

only)

CRPWREXH030A01

036-073*

1.6

N/A

0.64

15

CRPWREXH021A01

036-073

N/A

0.68

N/A

15

CRPWREXH022A01

090-151*

3.4

N/A

1.32

15

CRPWREXH023A01

090-151

N/A

1.4

N/A

15

CRPWREXH028A01

ALL*

1.7

N/A

0.68

15

CRPWREXH029A01

ALL

N/A

0.7

N/A

15

*Single or three phase.

77

Page 77
Image 77
Bryant 581A/B manual Unit Size Nominal IFM Voltage Range

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.