PERFORMANCE DATA (cont)

COOLING CAPACITIES — STANDARD UNITS (cont)

581A180 (15 Tons)

Temp (F)

 

 

 

 

 

 

 

 

 

Evap Air — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

4500/0.01

 

 

 

 

5250/0.01

 

 

 

 

6000/0.01

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air — Ewb (F)

 

 

 

 

 

 

 

 

 

Cond

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

58

62

67

72

76

80

54

58

62

67

72

76

80

54

58

62

67

72

76

80

 

TC

180.5

184.6

188.7

203.5

219.9

233.7

247

189.3

191.7

194.2

208.7

224.1

238

251

198.1

198.8

199.6

212.9

229.3

242

255

60

SHC

180.5

172.4

159.4

132.3

104.7

87.9

65.7

189.3

183.2

173.2

142.8

110.4

91

65.5

198.1

195.1

185.1

153.1

116.7

94

65.4

 

kW

9.41

9.49

9.58

9.87

10.19

10.47

10.78

9.58

9.63

9.68

9.97

10.29

10.57

10.87

9.75

9.77

9.79

10.07

10.39

10.67

10.95

 

TC

176.7

180.5

184.4

199

215.1

227.8

242

185.3

187.5

189.8

203

219.2

231.8

245

193

194.5

195.1

208.1

224.3

237

248

70

SHC

176.7

169

155.8

129.4

102.4

86

63.9

185.3

179.7

169.3

138.9

108

89.1

63.8

193

191.4

181

149.7

114.2

92.2

63.7

 

kW

10.5

10.57

10.64

10.96

11.35

11.62

11.95

10.68

10.72

10.76

11.06

11.45

11.72

12.04

10.85

10.87

10.89

11.17

11.55

11.82

12.13

 

TC

174.7

177.5

181

196

213

224.2

238

182.3

184.4

186

201

217

229.2

242

190.9

191.3

189

204

219

233.1

246

75

SHC

174.7

167.2

147

124

99

84.9

62.9

182.3

177.9

160

133

105

88

62.8

190.9

189.5

173

143

113

91

62.7

 

kW

11.07

11.14

11.2

11.6

12

12.23

12.57

11.25

11.3

11.3

11.7

12.1

12.33

12.66

11.45

11.45

11.4

11.8

12.1

12.44

12.75

 

TC

169.6

172.2

175

190

205

218.1

230.8

177.2

179

180

194

209

221.9

233.3

185.6

185.9

183

198

212

225.7

237

85

SHC

169.6

163.3

145

121

97

82.5

60.7

177.2

174.1

157

130

102

85.6

60.5

185.6

184.7

168

139

106

88.6

60.4

 

kW

12.29

12.35

12.3

12.7

13.1

13.5

13.86

12.47

12.51

12.5

12.8

13.2

13.61

13.96

12.67

12.68

12.6

12.9

13.3

13.71

14.05

 

TC

164.3

166.5

168

182

197

209.8

221.2

171.7

172.6

172

187

201

213.4

224.6

179.1

179.3

176

190

203

217.1

228

95

SHC

164.3

158.9

142

118

93

79.8

57.9

171.7

168.8

154

127

98

82.8

57.9

179.1

178.7

164

136

102

86

57.8

 

kW

13.59

13.65

13.5

13.9

14.3

14.85

15.23

13.8

13.82

13.6

14

14.4

14.96

15.32

14

14

13.8

14.1

14.5

15.07

15.43

 

TC

158.1

159.8

161

174

188

200.3

212.4

165.2

166

165

178

191

203.8

214.6

172.3

172.3

169

181

193

207.3

216.8

105

SHC

158.1

154.2

138

115

91

76.8

55.2

165.2

163.1

150

124

95

79.9

55.1

172.3

172.2

158

132

98

83

54.9

 

kW

14.97

15.02

14.8

15.2

15.6

16.28

16.69

15.19

15.21

14.9

15.3

15.7

16.39

16.77

15.41

15.4

15.1

15.4

15.7

16.5

16.86

 

TC

151.8

152.8

152

165

179

190.6

201.3

158.4

158.8

157

168

180

194

204.5

165

164.9

161

171

181

197.3

206.6

115

SHC

151.8

149.1

134

111

87

73.7

52.1

158.4

157

145

120

91

76.7

52.1

165

164.9

151

128

94

79.8

51.9

 

kW

16.45

16.48

16.1

16.5

16.9

17.79

18.21

16.68

16.68

16.2

16.6

17

17.91

18.3

16.89

16.88

16.4

16.7

17

18.01

18.39

 

TC

144.7

145.4

146

157.1

170.5

180.7

191.1

150.8

151.1

151.5

160.2

172.9

183.9

192

156.8

156.9

157

163.2

175.4

186.2

193.9

125

SHC

144.7

143.5

123.4

102.2

81.16

70.4

48.9

150.8

150.2

135.2

109.6

85.15

73.4

48.8

156.8

156.9

145.6

117.4

89.3

76.4

48.7

 

kW

17.96

18.01

18.05

18.49

18.99

19.44

19.85

18.18

18.22

18.25

18.6

19.11

19.5

19.89

18.42

18.44

18.46

18.72

19.14

19.65

19.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581A180 (15 Tons) (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Evap Air — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6750/0.01

 

 

 

 

7500/0.02

 

 

 

 

 

 

 

 

 

Air Ent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

Cond

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

58

62

67

72

76

80

54

58

62

67

72

76

80

 

 

 

 

 

 

 

 

TC

203.8

204.2

204.6

216.3

231.7

244

257

209.5

209.5

209.6

218.8

235

248

259

 

 

 

 

 

 

 

60

SHC

203.8

201.8

191.2

164.1

124.1

97

65.4

209.5

209.5

196.6

173.7

138.1

100

65.2

 

 

 

 

 

 

 

 

kW

9.88

9.88

9.89

10.13

10.45

10.72

11

9.99

9.99

9.99

10.19

10.51

10.78

11.05

 

 

 

 

 

 

 

 

TC

199.6

199.8

200.1

210.5

226.5

239

250

205.2

205.1

205.1

213.8

228.8

241

252

 

 

 

 

 

 

 

70

SHC

199.6

197.8

187

159.7

121.3

95.2

63.5

205.2

205.1

192.4

169.8

134.5

98.2

63.5

 

 

 

 

 

 

 

 

kW

10.99

10.99

11

11.24

11.6

11.88

12.18

11.12

11.11

11.11

11.31

11.65

11.94

12.22

 

 

 

 

 

 

 

 

TC

196.4

196.6

194

206

220

235

247

201.9

201.9

198

208

223

237

249

 

 

 

 

 

 

 

75

SHC

196.4

195.7

181

153

120

94

62.5

201.9

201.9

186

163

163

97.1

62.5

 

 

 

 

 

 

 

 

kW

11.58

11.58

11.6

11.9

12.2

12.5

12.8

11.71

11.7

11.7

11.9

11.9

12.56

12.84

 

 

 

 

 

 

 

 

TC

191

191.1

188

200

213

227.8

239

196.4

196.4

192

202

214

229.8

241

 

 

 

 

 

 

 

85

SHC

191

190.5

175

148

115

91.6

60.2

196.4

196.4

180

157

119

94.6

60.2

 

 

 

 

 

 

 

 

kW

12.81

12.81

12.7

13

13.3

13.77

14.1

12.96

12.95

12.8

13.1

13.4

13.84

14.13

 

 

 

 

 

 

 

 

TC

184.4

184.5

181

192

205

219.1

229.7

189.7

189.7

185

194

206

221.1

230.5

 

 

 

 

 

 

 

95

SHC

184.4

184.2

170

144

108

88.9

57.7

189.7

189.7

174

153

113

91.9

57.6

 

 

 

 

 

 

 

 

kW

14.15

14.15

13.9

14.2

14.6

15.14

15.47

14.29

14.29

14

14.3

14.6

15.2

15.51

 

 

 

 

 

 

 

 

TC

176.7

176.7

173

182

194

209.2

218.5

181.9

181.9

177

184

194

211.1

220.1

 

 

 

 

 

 

 

105

SHC

176.7

176.7

162

140

103

86

54.9

181.9

181.9

166

148

107

88.9

54.7

 

 

 

 

 

 

 

 

kW

15.55

15.55

15.2

15.5

15.8

16.57

16.9

15.7

15.7

15.3

15.5

15.8

16.64

16.94

 

 

 

 

 

 

 

 

TC

169.5

169.4

166

172

183

198.2

207.1

173.9

173.8

169

174

183

200

208.6

 

 

 

 

 

 

 

115

SHC

169.5

169.4

155

136

98

82.7

51.8

173.9

173.8

158

142

101

85.6

51.7

 

 

 

 

 

 

 

 

kW

17.05

17.04

16.6

16.8

17.1

18.08

18.42

17.2

17.2

16.7

16.9

17.1

18.15

18.45

 

 

 

 

 

 

 

 

TC

160.9

161.1

161.2

165.6

177.4

187.9

195.4

165.1

165.2

165.4

167.8

179.2

188.6

196

 

 

 

 

 

 

 

125

SHC

160.9

161.1

150.7

125.6

95.04

79.4

48.7

165.1

165.2

155.2

133.2

105.3

82.3

48.6

 

 

 

 

 

 

 

 

kW

18.57

18.59

18.62

18.81

19.18

19.68

20.06

18.72

18.75

18.78

18.91

19.33

19.71

20.09

 

 

 

 

 

 

 

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

 

1. Direct interpolation is permissible. Do not extrapolate.

2. The following formulas may be used:

tldb

= tedb

 

sensible capacity (Btuh)

 

 

 

1.10 x cfm

 

 

 

 

 

tlwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

 

 

rator coil (hlwb)

hlwb

= hewb

total capacity (Btuh)

 

4.5 x cfm

 

 

 

 

 

Where: hewb = Enthalpy of air entering evaporator coil

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

 

76

75

 

under 75

FACTOR

 

 

81

82

83

 

84

85

 

over 85

(BF)

 

 

 

 

 

 

 

Correction

Factor

 

 

.05

1.04

2.07

3.11

 

4.14

5.18

 

 

.10

.98

1.96

2.94

 

3.92

4.90

 

Use formula

.20

.87

1.74

2.62

 

3.49

4.36

 

shown below.

.30

.76

1.53

2.29

 

3.05

3.82

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

4. Use chart below for bypass factor.

 

 

 

ENTERING WET-BULB (F)

 

 

CFM

54

58

62

67

72

76

80

 

 

 

Bypass Factor

 

 

4500

0.396

0.193

0.054

0.053

0.067

0.000

0.000

5250

0.455

0.272

0.077

0.065

0.077

0.000

0.000

6000

0.504

0.337

0.121

0.077

0.088

0.000

0.000

6750

0.544

0.390

0.193

0.094

0.100

0.000

0.000

7500

0.578

0.436

0.244

0.108

0.114

0.000

0.000

581A155-300

209

Page 209
Image 209
Bryant 581A/B manual Performance Data, Cooling Capacities Standard Units

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.