Bryant 581A/B manual Performance Data cont, 580F180

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 189
Image 189

PERFORMANCE DATA (cont)\

FAN PERFORMANCE — 580F180-300 UNITS (cont)

580F300275 (25 TONS)*

Airflow

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

(Cfm)

 

0.2

 

 

 

0.4

 

 

 

0.6

 

 

0.8

 

 

1.0

 

 

1.2

 

 

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

941

3.35

 

2,769

1002

3.80

3,140

1061

 

4.27

3528

1117

4.76

3,934

1171

5.27

4,356

1224

5.80

4,794

7,500

999

4.05

 

3,348

1057

4.53

3,742

1112

 

5.02

4152

1166

5.54

4,579

1218

6.07

5,210

1268

6.63

5,478

8,000

1058

4.85

 

4,007

1113

5.35

4,424

1165

 

5.87

4856

1216

6.41

5,304

1266

6.97

5,766

1314

7.55

6,243

8,500

1117

5.74

 

4,750

1169

6.28

5,190

1219

 

6.83

5645

1268

7.40

6,114

1315

7.98

6,597

1361

8.58

7,094

9,000

1177

6.75

 

5,583

1226

7.31

6,047

1274

 

7.89

6524

1320

8.48

7,015

1365

9.09

7,520

1410

9.72

8,037

9,500

1237

7.98

 

6,511

1284

8.46

6,999

1329

 

9.07

7499

1374

9.69

8,012

1417

10.33

8,538

1459

10.98

9,076

10,000

1297

9.12

 

7,450

1342

9.74

8,051

1385

 

10.37

8574

1428

11.02

9,110

1469

11.68

9,657

1510

12.36

10,217

10,500

1358

10.49

 

8,674

1400

11.14

9,209

1442

 

11.80

9755

1483

12.47

10,314

1523

13.16

10,883

11,000

1418

12.00

 

9,919

1459

12.67

10,478

 

11,250

1449

12.80

 

10,585

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580F300275 (25 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

 

 

 

 

 

 

 

 

 

7,000

1274

6.35

 

5248

1323

6.92

5,718

1371

 

5.54

6204

 

 

 

 

 

 

 

 

 

7,500

1316

7.20

 

6960

1364

7.79

6,437

1410

 

6.41

6939

 

 

 

 

 

 

 

 

 

8,000

1360

8.14

 

6734

1406

8.76

7,239

1450

 

7.40

7759

 

 

 

 

 

 

 

 

 

8,500

1406

9.20

 

7605

1449

9.83

8,129

1492

 

8.48

8666

 

 

 

 

 

 

 

 

 

9,000

1453

10.36

 

8568

1495

11.02

9,111

1536

 

9.69

9667

 

 

 

 

 

 

 

 

 

9,500

1501

11.64

 

9627

1541

12.32

10,190

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

10,500

 

 

 

 

 

 

 

 

 

 

 

11,000

 

 

 

 

 

 

 

 

 

 

 

11,250

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

Refer to this page for general Fan Performance Data notes.

 

 

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Performance table for more information.

580F300360 (25 TONS)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

(Cfm)

 

0.2

 

 

 

0.4

 

 

 

0.6

 

 

0.8

 

 

1.0

 

 

1.2

 

 

 

 

 

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

7,000

992

4.05

 

3,348

1051

4.44

3,668

1106

 

4.83

3995

1160

5.24

4331

1212

5.65

4675

1262

6.08

5026

 

 

 

7,500

1055

4.77

 

3,947

1110

5.17

4,277

1162

 

5.58

4615

1214

6.00

4960

1263

6.43

5312

1311

6.86

5672

 

 

 

8,000

1118

5.58

 

4,610

1170

5.99

4,950

1220

 

6.41

5298

1268

6.84

5653

1315

7.27

6014

1361

7.72

6382

 

 

 

8,500

1182

6.46

 

5,339

1231

6.88

5,690

1278

 

7.31

6047

1324

7.75

6411

1369

8.20

6782

1413

8.66

7158

 

 

 

9,000

1246

7.42

 

6,136

1292

7.86

6,498

1337

 

8.30

6865

1381

8.75

7239

1424

9.21

7618

1466

9.68

8003

 

 

 

9,500

1310

8.47

 

7,005

1354

8.92

7,377

1397

 

9.38

7754

1439

9.84

8137

1480

10.31

8525

1520

10.79

8918

 

 

 

10,000

1374

9.61

 

7,947

1416

10.07

8,329

1457

 

10.54

8715

1497

11.02

9107

1537

11.50

9504

 

 

 

10,500

1439

10.84

 

8,964

1479

11.32

9,356

1518

 

11.79

9752

 

 

 

11,000

1503

12.17

 

10,059

1542

12.65

10,460

 

 

 

 

11,250

1536

12.86

 

10,636

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580F300360 (25 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580F180-

 

7,500

1358

7.30

6039

1403

7.76

6412

1448

 

6.84

6792

 

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

Available External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

1.4

 

 

 

1.6

 

 

 

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

 

Bhp

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7,000

1311

6.51

 

5385

1359

6.96

5751

1405

 

6.00

6124

 

 

 

 

 

 

 

 

 

 

300

 

8,000

1406

8.17

 

6767

1560

8.63

7137

1492

 

7.75

7524

 

 

 

 

 

 

 

 

 

 

8,500

1456

9.12

 

7541

1498

9.59

7929

1539

 

8.75

8323

 

 

 

 

 

 

 

 

 

 

 

 

9,000

1507

10.15

 

8393

1548

10.63

8790

 

 

 

 

 

 

 

 

 

 

 

 

 

9,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11,250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower

Watts — Input Watts to Motor

*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high- static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

Refer to this page for general Fan Performance Data notes.

NOTE: Maximum continuous bhp is 10.20 (208/230 and 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230 and 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Performance table for more information.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1.Static pressure losses (i.e., EconoMi$er IV) must be added to external static pressure before entering Fan Performance table.

2.Interpolation is permissible. Do not extrapolate.

3.Fan performance is based on wet coils, clean filters, and casing losses. See Accessory/FIOP Static Pressure table on page 191.

4.Extensive motor and drive testing on these units ensures that the full horse- power and watts range of the motor can be utilized with confidence. Using fan motors up to the watts or bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

5.Use of a field-supplied motor may affect wire size. Contact your Bryant rep- resentative for details.

189

Page 189
Image 189
Bryant 581A/B manual Performance Data cont, 580F180