Bryant 581A/B manual 581A300 25 Tons Unit with HOT GAS Reheat in Cooling Mode

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 217
Image 217

PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont)

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT IN COOLING MODE

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering

 

 

 

7000/0.042

 

 

 

 

8250/0.052

 

 

 

 

 

9500/0.062

 

 

 

 

 

10,750/0.072

 

 

 

12,000/0.082

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator — Ewb (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

 

62

 

67

 

72

57

 

62

 

67

72

 

57

 

62

 

67

 

72

57

 

62

 

67

 

72

57

62

 

67

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

245

 

268

 

293

 

318

259

 

282

303

333

 

274

 

291

 

314

 

340

289

 

301

 

322

 

348

305

309

 

332

356

 

SHC

 

245

 

229

 

197

 

162

259

 

254

213

173

 

274

 

271

 

230

 

183

289

 

287

 

247

 

195

305

298

 

267

203

 

 

kW

 

16.4

 

17.0

17.6

 

18.2

16.7

 

17.4

17.9

18.6

 

17.1

 

17.6

 

18.2

 

18.8

17.5

 

17.8

 

18.4

 

19.0

18.0

18.1

 

18.6

19.2

85

 

TC

 

233

 

259

 

278

 

309

256

 

273

293

324

 

271

 

282

 

305

 

330

285

 

290

 

312

 

337

298

303

 

321

343

 

SHC

 

233

 

228

 

186

 

158

256

 

252

211

171

 

271

 

264

 

229

 

180

285

 

276

 

246

 

191

298

295

 

261

201

 

 

kW

 

17.9

 

18.7

19.3

 

19.9

18.5

 

19.1

19.7

20.4

 

19.0

 

19.4

 

20.0

 

20.8

19.3

 

19.6

 

20.2

 

21.1

19.8

19.9

 

20.4

21.3

95

 

TC

 

230

 

252

 

276

 

303

251

 

265

284

314

 

269

 

274

 

290

 

326

274

 

282

 

300

 

332

283

293

 

308

334

 

SHC

 

230

 

225

 

191

 

156

251

 

249

202

166

 

269

 

269

 

220

 

181

274

 

274

 

238

 

190

283

280

 

259

197

 

 

kW

 

20.0

 

20.8

21.4

 

22.1

20.7

 

21.2

21.5

22.4

 

21.3

 

21.4

 

21.9

 

23.0

21.5

 

21.7

 

22.1

 

23.2

21.6

22.0

 

22.5

23.3

105

 

TC

 

226

 

245

 

268

 

292

242

 

253

277

301

 

255

 

264

 

284

 

308

266

 

275

 

290

 

314

278

281

 

294

319

 

SHC

 

226

 

223

 

188

 

153

242

 

241

205

163

 

255

 

255

 

221

 

171

265

 

265

 

240

 

185

278

278

 

253

194

 

 

kW

 

22.0

 

22.8

23.3

 

24.3

22.7

 

23.1

23.7

24.7

 

23.1

 

23.4

 

24.0

 

25.0

23.6

 

23.7

 

24.3

 

25.2

24.0

24.1

 

24.4

25.4

115

 

TC

 

221

 

233

 

258

 

281

232

 

242

267

290

 

247

 

253

 

274

 

297

253

 

260

 

275

 

302

267

269

 

279

306

 

SHC

 

221

 

217

 

183

 

149

232

 

230

200

160

 

247

 

246

 

217

 

170

253

 

254

 

233

 

179

267

267

 

248

189

 

 

kW

 

24.3

 

25.1

25.7

 

26.7

24.8

 

25.4

26.1

27.1

 

25.3

 

25.8

 

26.4

 

27.2

25.8

 

26.0

 

26.5

 

27.3

26.1

26.3

 

26.7

27.4

125

 

TC

 

216

 

223

 

247

 

268

225

 

230

253

275

 

237

 

240

 

256

 

280

247

 

248

 

260

 

285

254

255

 

263

288

 

SHC

 

216

 

212

 

181

 

145

225

 

223

196

155

 

237

 

236

 

211

 

163

247

 

247

 

228

 

174

254

254

 

242

184

 

 

kW

 

26.9

 

27.1

28.0

 

29.0

27.4

 

27.5

28.3

29.4

 

27.8

 

27.9

 

28.5

 

29.6

28.2

 

28.3

 

28.7

 

29.8

28.5

28.6

 

28.9

29.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering

 

 

7500/0.045

 

 

 

8250/0.055

 

 

 

 

 

9500/0.065

 

 

 

 

10,750/0.075

 

 

 

12,000/0.085

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air — Relative Humidity (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

55

 

60

 

 

50

 

55

60

 

 

50

 

 

55

 

60

 

50

 

 

 

55

 

60

 

50

 

 

55

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

 

79

 

83

 

87

 

 

80

 

84

88

 

 

81

 

 

85

 

89

 

82

 

 

86

 

90

 

83

 

 

87

 

91

65

 

SHC

 

 

39

 

33

 

28

 

 

41

 

35

30

 

 

43

 

 

37

 

32

 

45

 

 

39

 

34

 

47

 

 

41

 

36

 

 

kW

 

 

11

 

11

 

11

 

 

11

 

11

11

 

 

11

 

 

11

 

11

 

11

 

 

11

 

11

 

11

 

 

11

 

11

 

 

TC

 

 

56

 

61

 

65

 

 

57

 

62

66

 

 

59

 

 

63

 

67

 

60

 

 

64

 

68

 

61

 

 

65

 

69

75

 

SHC

 

 

18

 

11

 

5

 

 

20

 

12

6

 

 

22

 

 

15

 

8

 

24

 

 

16

 

10

 

26

 

 

18

 

12

 

 

kW

 

 

11

 

11

 

11

 

 

11

 

11

11

 

 

11

 

 

11

 

11

 

11

 

 

11

 

11

 

11

 

 

11

 

11

 

 

TC

 

 

34

 

38

 

42

 

 

35

 

39

43

 

 

37

 

 

41

 

45

 

38

 

 

42

 

46

 

39

 

 

43

 

47

85

 

SHC

 

 

–2

 

–11

 

–19

 

 

–1

 

–10

–18

 

1

 

 

 

–8

 

–16

 

3

 

 

 

–7

 

–14

 

4

 

 

–5

 

–13

 

 

kW

 

 

11

 

11

 

12

 

 

11

 

12

12

 

 

12

 

 

12

 

12

 

12

 

 

12

 

12

 

12

 

 

12

 

12

 

 

TC

 

 

12

 

16

 

19

 

 

13

 

17

21

 

 

15

 

 

19

 

22

 

16

 

 

20

 

24

 

17

 

 

22

 

25

95

 

SHC

 

 

–23

 

–33

 

–42

 

–22

 

–32

–41

 

–20

 

 

–31

 

–40

 

–19

 

 

–30

 

–39

 

–17

 

–28

 

–38

 

 

kW

 

 

12

 

12

 

12

 

 

12

 

12

12

 

 

12

 

 

12

 

12

 

12

 

 

12

 

12

 

12

 

 

12

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

581A300 (25 TONS) UNIT WITH HOT GAS REHEAT — A IN REHEAT, B ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air Quantity — Cfm/BF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering

 

 

7500/0.045

 

 

 

8250/0.055

 

 

 

 

 

9500/0.065

 

 

 

 

10,750/0.075

 

 

 

12,000/0.085

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air — Relative Humidity (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

55

 

60

 

 

50

 

55

60

 

 

50

 

 

55

 

60

 

50

 

 

 

55

 

60

 

50

 

 

55

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

 

 

211

 

222

 

231

 

215

 

226

235

 

 

220

 

 

232

 

241

 

226

 

 

237

 

247

 

230

 

 

242

 

252

65

 

SHC

 

 

123

 

115

 

109

 

129

 

121

115

 

 

139

 

 

131

 

124

 

147

 

 

139

 

133

 

155

 

 

147

 

140

 

 

kW

 

 

19

 

19

 

20

 

 

19

 

19

20

 

 

19

 

 

19

 

20

 

19

 

 

 

20

 

20

 

19

 

 

20

 

20

 

 

TC

 

 

182

 

193

 

202

 

185

 

196

205

 

 

189

 

 

200

 

210

 

192

 

 

204

 

214

 

196

 

 

208

 

218

75

 

SHC

 

 

103

 

93

 

85

 

110

 

100

91

 

 

120

 

 

110

 

101

 

128

 

 

118

 

110

 

136

 

 

126

 

118

 

 

kW

 

 

20

 

21

 

21

 

 

20

 

21

21

 

 

21

 

 

21

 

21

 

21

 

 

 

21

 

21

 

21

 

 

21

 

21

 

 

TC

 

 

153

 

164

 

174

 

155

 

166

176

 

 

157

 

 

169

 

178

 

159

 

 

171

 

181

 

161

 

 

173

 

184

85

 

SHC

 

 

84

 

72

 

62

 

 

90

 

78

68

 

 

100

 

 

88

 

78

 

110

 

 

97

 

87

 

118

 

 

106

 

95

 

 

kW

 

 

22

 

22

 

22

 

 

22

 

22

22

 

 

22

 

 

22

 

22

 

22

 

 

 

22

 

22

 

22

 

 

22

 

22

 

 

TC

 

 

124

 

135

 

145

 

125

 

136

146

 

 

125

 

 

137

 

147

 

126

 

 

138

 

148

 

127

 

 

139

 

149

95

 

SHC

 

 

64

 

50

 

38

 

 

71

 

57

45

 

 

81

 

 

67

 

55

 

91

 

 

 

76

 

64

 

99

 

 

85

 

72

 

 

kW

 

 

23

 

23

 

23

 

 

23

 

23

23

 

 

23

 

 

23

 

24

 

23

 

 

 

23

 

24

 

23

 

 

24

 

24

 

 

LEGEND

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb —

Entering Wet-Bulb

kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC —

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity (Btuh)

tldb = tedb 1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo- rator coil (hlwb)

3.The SHC is based on 80 F edb temperature of air entering evaporator coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

 

 

 

 

 

 

 

 

 

581A155

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

 

 

79

78

77

 

76

75

 

under 75

 

FACTOR

 

 

 

81

82

83

 

84

85

 

over 85

 

(BF)

 

 

 

 

 

 

 

Correction Factor

 

-300

.05

1.04

2.07

3.11

 

4.14

5.18

 

Use formula

.10

.98

1.96

2.94

 

3.92

4.90

 

 

.20

.87

1.74

2.62

 

3.49

4.36

 

shown below.

 

.30

.76

1.53

2.29

 

3.05

3.82

 

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

total capacity (Btuh)

hlwb = hewb 4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

217

Page 217
Image 217
Bryant 581A/B manual 581A300 25 Tons Unit with HOT GAS Reheat in Cooling Mode

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.