Bryant 581A/B ARI* Capacity Ratings 580F180-300, Heating Capacities and Efficiencies 580F180-300

Models: 581A/B

1 268
Download 268 pages 21.01 Kb
Page 13
Image 13

ARI* CAPACITY RATINGS — 580F180-300

UNIT SIZE

NOMINAL

NET COOLING

TOTAL

 

SOUND

 

580F

EER

RATING

IPLV

TONS

CAPACITY (Btuh)

WATTS

(Low Heat)

 

(dB)

 

 

 

 

 

 

180

15

176,000

17,064

9.5

88

9.5

210

18

202,000

21,166

9.7

88

10.2

240

20

236,000

24,832

9.5

94

10.1

300

25

278,000

28,535

9.7

94

10.4

 

 

 

 

 

 

 

UNIT SIZE

NOMINAL

NET COOLING

TOTAL

 

SOUND

 

580F

EER

RATING

IPLV

TONS

CAPACITY (Btuh)

WATTS

(High Heat)

 

(dB)

 

 

 

 

 

 

180

15

176,000

17,179

9.5

88

9.5

210

18

202,000

21,301

9.7

88

10.1

240

20

236,000

24,832

9.5

94

10.0

300

25

277,000

29,067

9.5

94

10.0

 

LEGEND

Bels

Sound Levels (1 bel = 10 decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio

IPLV

Integrated Part-Load Values

wb

Wet Bulb

*Air Conditioning and Refrigeration Institute.

NOTES:

1.Rated in accordance with ARI Standards 360 and 270.

2.ARI ratings are net values, reflecting the effects of circulating fan heat.

3.Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db air entering outdoor unit.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

4.All 580F180-300 units are in compliance with ASHRAE 90.1- 1999 Energy Standard for minimum SEER and EER require- ments. Refer to state and local codes or visit the following website: http://solstice.crest.org/efficiency/bcap to determine if compliance with this standard pertains to a given geographical area of the United States.

HEATING CAPACITIES AND EFFICIENCIES — 580F180-300

UNIT

HEATING INPUT

OUTPUT CAPACITY

TEMPERATURE

STEADY-STATE

MINIMUM

(Btuh)

580F

(Btuh)

RISE (F)

EFFICIENCY (%)

HEATING CFM

Stage 2/Stage 1*

 

 

 

 

 

180275

275,000/206,000

223,000

15-45

81.0

3750

180360

360,000/270,000

292,000

20-50

81.0

3830

210275

275,000/206,000

223,000

15-45

81.0

4580

210360

360,000/270,000

292,000

20-50

81.0

5400

240275

275,000/206,000

223,000

15-45

81.0

4580

240360

360,000/270,000

292,000

20-50

81.0

5400

300275

275,000/206,000

223,000

15-45

81.0

4580

300360

360,000/270,000

292,000

20-50

81.0

5400

*All units are 2-stage heat.

NOTE: Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating. For entering-air temperatures below 45 F both stages of heat must be energized together to minimize condensation issues and ensure proper unit operation.

AIR QUANTITY LIMITS (Cooling)

UNIT 580F

MINIMUM CFM

MAXIMUM CFM

180

4500

7,500

210

5400

9,000

240

6000

10,000

300

7000

11,250

COOLING OPERATION

LOW OUTDOOR TEMPERATURE OPERATING LIMITS (F)

UNITS

TEMPERATURE

All — Standard Unit

40

180 and 210 with Low Ambient Kit

10

240 and 300 with Low Ambient Kit

25

All with Motormaster® Head Pressure Control

–20

13

Page 13