PERFORMANCE DATA (cont)

FAN RPM AT MOTOR PULLEY SETTINGS* — 580F036-073

UNIT 580F

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

0

1/2

1

11/2

2

21/2

 

3

31/2

4

41/2

5

51/2

6

 

 

036†

1045

1009

973

937

901

865

 

829

793

757

721

685

036**

1455

1423

1392

1360

1328

1297

 

1265

1233

1202

1170

1138

1107

1075

048†

1175

1135

1094

1054

1013

973

 

932

892

851

811

770

048**

1455

1423

1392

1360

1328

1297

 

1265

1233

1202

1170

1138

1107

1075

060†

1300

1266

1233

1200

1166

1133

 

1100

1066

1033

1000

966

933

900

060**

1685

1647

1608

1570

1531

1493

 

1454

1416

1377

1339

1300

072,073††

1460

1421

1382

1343

1304

1265

 

1226

1187

1148

1109

1070

072,073**

1685

1647

1608

1570

1531

1493

 

1454

1416

1377

1399

1300

*Approximate fan rpm shown.

 

 

 

 

 

**Indicates high-static motor and drive package.

 

 

 

†Indicates alternate motor and drive package.

 

 

 

 

††Indicates standard motor and drive package.

 

 

 

580F036-151

FAN RPM AT MOTOR PULLEY SETTINGS* — 580F090-151

UNIT 580F

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

0

1/2

1

11/2

2

 

21/2

3

31/2

4

41/2

5

51/2

6

 

 

090,091†

840

815

790

765

740

 

715

690

665

635

615

590

090,091**

935

910

885

860

835

 

810

785

760

735

710

685

090,091††

1080

1025

1007

988

970

 

952

933

915

897

878

860

103†

935

910

885

860

835

 

810

785

760

735

710

685

103††

1080

1025

1007

988

970

 

952

933

915

897

878

860

120,121†

935

910

885

860

835

 

810

785

760

735

710

685

120,121***

1085

1060

1035

1010

985

 

960

935

910

885

860

835

120,121††

1130

1112

1087

1062

1037

 

1012

987

962

937

912

887

862

830

150,151†

1080

1060

1035

1015

990

 

970

950

925

905

880

860

150,151***

1130

1112

1087

1062

1037

 

1012

987

962

937

912

887

862

830

*Approximate fan rpm shown.

†Indicates standard motor and drive package. **Indicates alternate drive package only.

††Indicates high-static motor and drive package.

***Indicates alternate motor and drive package.

ALTITUDE COMPENSATION* — 580F036-073

STANDARD UNITS

 

74,000 AND 115,000 BTUH

150,000 BTUH

ELEVATION

NOMINAL INPUT

NOMINAL INPUT

(ft)

Natural Gas

Liquid Propane

Natural Gas

Liquid Propane

 

Orifice Size†

Orifice Size†

Orifice Size†

Orifice Size†

0-2,000

33

43

30

37

2,000

36

44

31

39

3,000

36

45

31

40

4,000

37

45

32

41

5,000

38

46

32

42

6,000

40

47

34

43

7,000

41

48

35

43

8,000

42

49

36

44

9,000

43

50

37

45

10,000

44

50

39

46

11,000

45

51

41

47

12,000

46

52

42

48

13,000

47

52

43

49

14,000

48

53

44

50

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your local Bryant distributor.

ALTITUDE COMPENSATION* — 580F036-073

LOW NOx UNITS

ELEVATION

60,000 AND 90,000 BTUH

120,000 BTUH

NOMINAL INPUT

NOMINAL INPUT

(ft)

Natural Gas Orifice Size†

Natural Gas Orifice Size

 

0-2,000

38

32

2,000

40

33

3,000

41

35

4,000

42

36

5,000

43

37

6,000

43

38

7,000

44

39

8,000

45

41

9,000

46

42

10,000

47

43

11,000

48

44

12,000

49

44

13,000

50

46

14,000

51

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes.

†Orifices are available through your local Bryant distributor.

ALTITUDE COMPENSATION* — 580F090-151

 

125,000,180,000, AND 224,000

250,000 BTUH

ELEVATION

BTUH NOMINAL INPUT

NOMINAL INPUT

(ft)

Natural Gas

Liquid Propane

Natural Gas

Liquid Propane

 

Orifice Size†

Orifice Size†

Orifice Size†

Orifice Size†

0-2,000

31

41

30

38

2,000

32

42

30

39

3,000

32

42

31

40

4,000

32

42

32

41

5,000

33

43

33

42

6,000

34

43

34

43

7,000

35

44

35

43

8,000

36

44

36

44

9,000

37

45

37

44

10,000

38

46

38

45

11,000

39

47

39

45

12,000

40

47

40

46

13,000

41

48

41

47

14,000

42

48

42

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

†Orifices available through your local Bryant distributor.

ALTITUDE DERATING FACTOR*

ELEVATION

MAXIMUM HEATING VALUE

(ft)

(Btu/ft3)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

*Derating of the unit is not required unless the heating value of the gas exceeds the val- ues listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above 2000 ft. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

IMPORTANT: Local utility companies may be reducing heat content of gas at altitudes above 2000 ft. If this is being done, changing spuds may not be required.

71

Page 71
Image 71
Bryant 581A/B manual FAN RPM AT Motor Pulley SETTINGS* 580F036-073, FAN RPM AT Motor Pulley SETTINGS* 580F090-151

581A/B specifications

The Bryant 581A/B is a sophisticated rooftop unit designed for commercial heating and cooling applications, striking a balance between performance, efficiency, and versatility. This unit is engineered to cater to various building sizes and configurations, making it an excellent choice for businesses seeking reliable climate control solutions.

One of the standout features of the Bryant 581A/B is its high efficiency. With SEER ratings reaching up to 14.5, this unit can significantly reduce energy costs while providing optimal performance throughout its operational lifespan. The design incorporates advanced compressor technology, allowing for variable speed operation that not only enhances comfort but also promotes energy savings by adjusting to the real-time demands of the environment.

The Bryant 581A/B also integrates cutting-edge refrigerant technology. Utilizing Puron refrigerant, it adheres to current environmental standards, minimizing its impact on ozone depletion while maximizing cooling performance. This commitment to sustainability is complemented by energy-efficient components, including high-efficiency coils and fan motors, which further optimize energy consumption.

In terms of construction, the Bryant 581A/B is built to withstand the rigors of outdoor installation. The unit features a rugged cabinet design with durable, corrosion-resistant materials, ensuring long-term reliability even in challenging weather conditions. Additionally, the easily accessible components simplify maintenance, reducing downtime for businesses.

The functionality of the Bryant 581A/B extends beyond mere cooling and heating. It is equipped with advanced control systems that can be interfaced with building management systems, allowing for seamless integration and enhanced control over indoor climate. This technology provides operators with the ability to monitor and adjust settings remotely, ensuring a comfortable indoor environment while optimizing energy use.

Noise reduction is another important characteristic of the Bryant 581A/B. The unit is designed with sound-dampening features, making it suitable for applications where low noise levels are a priority, such as retail spaces or office buildings.

Overall, the Bryant 581A/B is a robust solution for businesses seeking efficient, reliable, and flexible climate control. Its combination of advanced technology, durable construction, and user-friendly features make it a leading choice in the commercial HVAC market.