Fedders F80A dimensions Warm Air Furnace, Troubleshooting

Models: F80A

1 32
Download 32 pages 57.83 Kb
Page 23
Image 23
TROUBLESHOOTING

WARM AIR FURNACE

TROUBLESHOOTING

SEQUENCE OF OPERATION: WHITE RODGERS INTEGRATED FURNACE CONTROL WITH WHITE RODGERS 36G22 GAS VALVE

APPLY POWER TO APPLIANCE

THERMOSTAT CALLS FOR HEAT

AIR PROVING SWITCH PROVED OPEN?

YES

COMBUSTION AIR BLOWER ON

AIR PROVING SWITCH PROVED CLOSED

YES

NO

NO

WAIT FOR AIR PROVING SWITCH TO OPEN

FIVE MINUTE WAIT PERIOD

COMBUSTION AIR BLOWER OFF

PREPURGE

HOT SURFACE IGNITER ON FOR WARM-UP TIME

MAIN VALVE OPENS

HOT SURFACE IGNITER OFF

MAIN BURNER LIGHTS AND IS SENSED DURING TRIAL FOR IGNITION?

YES

CIRCULATING AIR FAN ON AFTER DELAY

FLAME SENSE LOST?

NO

THERMOSTAT CALL FOR HEAT ENDS

MAIN VALVE CLOSES

COMBUSTION AIR BLOWER OFF AFTER POST PURGE

NO

YES

BETWEEN TRIAL PURGE

 

 

 

 

 

HOT SURFACE IGNITER OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN VALVE CLOSES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

YES

 

 

 

TRIALS FOR IGNITION LESS THAN FOUR

COMBUSTION AIR BLOWER OFF

 

 

 

DURNG THIS IGNITION SEQUENCE?

 

 

 

AFTER POST PURGE

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN VALVE CLOSES

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME SENSE LOST MORE THAN FIVE

 

 

 

 

 

 

 

 

 

TIMES IN THIS CALL FOR HEAT?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCULATING AIR FAN OFF AFTER DELAY

WAIT FOR NEXT CALL FOR HEAT

22

Page 23
Image 23
Fedders F80A dimensions Warm Air Furnace, Troubleshooting