| WARM AIR FURNACE | ||
| TABLE 11: GENERAL TROUBLESHOOTING |
|
| ||||||||||
|
| IF |
|
|
| AND |
|
|
|
| CHECK or REPAIR |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Induced blower | does | 2 Flash code does not come on | 1. | Induced blower wiring. |
|
| ||||||
| not energize |
|
|
|
|
|
|
| 2. | Induced blower. |
|
| |
| Induced blower | does | 2 Flash code | does | come on |
| 1. | Pressure switch stuck closed. |
|
| |||
| not energize |
|
|
|
|
|
|
| 2. | Pressure switch is |
|
| |
| Induced blower is | 3 Flash code | does | not | come | on | Wait for the |
|
| ||||
| energized |
|
| Induced blower turns off |
|
| 1. | Pressure switch stuck in the open position. |
|
| |||
| 3 Flash code |
|
|
|
|
|
| ||||||
| comes on |
|
|
|
|
|
|
| 2. | Pressure switch, tubing and wiring. |
|
| |
|
|
|
|
|
|
|
|
|
| 3. | Obstruction in furnace venting that is preventing proper combustion airflow. |
| |
| HSI element | does not | glow | red | 1. | Broken or damaged HSI element. |
|
| |||||
| 2. | Broken or damaged HSI element leadwires. |
|
| |||||||||
| expired |
|
| within 10 seconds. |
|
|
|
|
| ||||
| HSI element is | glow- | No other visible control system | Wait for HSI element warm up time to expire. |
|
| |||||||
| ing red. |
|
| action |
|
|
|
| 1. | Induced blower moving main burner gas away from the HSI element. |
|
| |
| HSI element warm up |
|
|
|
|
|
|
| |||||
| Main valve does not light within | 2. | Inlet gas pressure too low for main burner ignition. |
|
| ||||||||
| time has expired and | 3. | Input line voltage too low to heat HSI element. |
|
| ||||||||
| main | valve has | been | trial for ignition period |
|
|
|
| |||||
| energized. |
|
|
|
|
|
|
| 4. | HSI element incorrectly positioned. |
|
| |
|
|
|
|
| Main valve is | 5. | Clogged or incorrect main burner orifice. |
|
| ||||
|
|
|
|
| 1. | Line voltage to L1 terminal of |
| ||||||
|
|
|
|
| end of the trial for ignition period. | 2. | chassis. |
|
| ||||
| Main | burner |
| lights | If main flame is not sensed during | Furnace must be reliably connected to earth ground. |
|
| |||||
|
| trial for ignition, system will shut off | 3. | Induced blower moving main burner flame away from the flame sensor rod. |
| ||||||||
| within trial for ignition | HSI element and main gas flow, |
| ||||||||||
| period. |
|
| then go through another purge |
| 4. | Inlet gas pressure too low for proper flame sensing. |
|
| ||||
|
|
|
|
| period and initiate another ignition | 5. | Flame sensor rod contaminated or in incorrect position. |
|
| ||||
|
|
|
|
| trial. A total of 4 ignition | trials | will |
|
| ||||
|
|
|
|
| be attempted before the system |
|
|
|
| ||||
| Main burner stays on | goes into lockout. |
|
|
|
|
|
|
| ||||
| Circulating fan is not turned on after | 1. | Wiring between system control and IFC. Proper operation of |
| |||||||||
| after | the end | of the |
| |||||||||
| trial for ignition pe- |
|
|
|
|
|
| ||||||
| riod. |
|
|
|
|
|
|
|
| 1. | Open high limit switch. |
|
|
| Main burner goes out | 4 Flash code comes on |
|
|
|
| |||||||
| before thermostat call |
|
| 2. | High limit wiring in good condition and securely connected. |
|
| ||||||
| for heat ends. |
|
|
|
|
|
|
| 1. |
|
|
| |
|
|
|
|
|
|
|
|
|
| Induced blower moving main burner flame away from flame sensor rod. |
| ||
| Main burner goes out | 4 Flash code does not come on |
| 2. | Pressure switch has opened. |
|
| ||||||
| before thermostat call |
| 3. | Flame sensor rod ceramic or leadwire overheated. |
|
| |||||||
| for heat ends. |
|
|
|
|
|
|
| 4. | Gas supply / flow reduced or interrupted. |
|
| |
| 5 Flash code | comes |
|
|
|
|
| 1. | Open flame rollout switch |
|
| ||
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
| 2. | Rollout switch wiring in good condition |
|
| ||||
| on. |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| 1. | Gas supply off or at too low a pressure to operate furnace. |
|
|
| 1 Flash code | comes |
|
|
|
|
| 2. | Damaged or broken HSI element. | reference to the |
| ||
|
|
|
|
|
| 3. | Line voltage to L1 terminal of |
| |||||
| on. | lockout |
|
|
|
|
| 4. | furnace chassis. |
|
| ||
| After |
|
|
|
|
| Furnace is not properly connected to earth ground. |
|
| ||||
| reset | delay, | control |
|
|
|
|
| 5. | Flame rod contaminated or in incorrect location. |
|
| |
| will reset and initiate |
|
|
|
|
|
|
| |||||
| a new ignition se- |
|
|
|
|
| 6. | Hot surface element located in incorrect position. |
|
| |||
| quence if the | call for |
|
|
|
|
| 7. | Hot surface element or flame sensing rod wiring in good condition and properly con- |
| |||
| heat is still present. |
|
|
|
|
|
| ||||||
|
|
|
|
|
| 8. | nected. | within the |
| ||||
|
|
|
|
|
|
|
|
|
| 5 flame failures caused by opening limit switch or flame rollout switch, |
| ||
|
|
|
|
|
|
|
|
|
|
| thermostat call for heat. Turn thermostat down below room temperature to reset |
| |
|
|
|
|
|
|
|
|
|
|
| control. Check for blocked air filter, closed ducts, etc. |
|
|
24