255 the Optomux literature should be read for additional

 

 

 

information as these are codes returned by the Optomux device.

 

 

 

 

 

128

Nak from Optomux Device. Power Up Clear Expected. Command

 

 

 

Ignored.

 

 

129

Nak from Optomux Device. Undefined Command

 

 

130

Nak from Optomux Device. Checksum Error

 

 

131

Nak from Optomux Device. Input Buffer Overun

 

 

132

Nak from Optomux Device. Non Printable Ascii character received

 

 

133

Nak from Optomux Device. Data Field Error

 

 

134

Nak from Optomux Device. Communication watchdog timeout

 

 

135

Nak from Optomux Device. Specified limits invalid.

 

 

 

The following codes are generated by the driver. They all indicate

 

 

 

errors.

 

 

 

 

 

250

An ack with no data was expected. Ack with Data was received.

 

 

251

The driver Complete function returned an error, could be

 

 

 

checksum, bad 1st char ... ie. The message was badly formatted.

 

 

252

Driver Timeout

 

 

253

An ack was received but it was badly formatted

 

 

254

A nak was received but was badly formatted

 

 

255

Message was not acknowledged correctly.

 

 

 

 

 

 

 

 

 

6.4Optomux Commands

The following provides a list of commands supported by the driver. The Command Name’s provided in the table must be used in providing values for the opto22_function parameter. The notes provided only apply when module positions are specified dynamically.