4.4.9Map Descriptor Example 6 – Using a Mask to Address specific module positions

There may be occasions when it is not suitable to use address and length. For example if you are attempting to address non-consecutive Optomux module positions OR when you wish to use a command that affects all module positions. The driver provides an alternate method for module position specification by allowing you to specify a mask as a parameter in the CSV file. The mask may be specified in decimal or hexadecimal format.

In this example, module positions 1 and 5 are pulsed.

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Length, Scan_Interval, opto22_mask, opto22_function

PULSE77

, TIME_DATA , 0

, wrbc , DEV77 , 1 , 10.0s

, 0x0011 , START ON PULSE

Module positions are specified in hexadecimal in this example.

0x0001

= Module Position 1

0x0002

= Module Position 2

0x0003

= Module Positions 1 & 2

…..

 

This function turned on the specified module positions for a specified period. Un specified positions (mask bit positions equal zero) are non affected by the command.