FS-8700-17 Optomux

Driver Manual

4 Configuring the FieldServer as a Optomux Driver Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with an Optomux Device.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Optomux Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1 Data Arrays

Section Title

 

 

Data_Arrays

 

 

Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

 

characters

Data_Format

Provide data format. Each data array can

FLOAT, BIT, UInt16, SInt16,

 

only take on one format.

Packed_Bit, Byte,

 

 

Packed_Byte,

 

 

Swapped_Byte

Data_Array_Length

Number of Data Objects. Must be larger

1-10,000

 

than the data storage area required for

 

 

the data being placed in this array.

 

 

 

 

Example

//Data Arrays

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length

DA_AI_01,

UInt16,

200

DA_AO_01,

UInt16,

200

DA_DI_01,

Bit,

200

DA_DO_01,

Bit,

200