FS-8700-17 Optomux

Driver Manual

4.2Client Side Connections

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Port

Specify which port the device is

R1-R2, (FS-X40 Series)

 

connected to the FieldServer

R1 (FS-X20 Series)

Baud*

Specify baud rate

110 – 115200, standard baud

 

 

rates only

 

 

At the time of publication of this

 

 

manual the OPTO22 device’s

 

 

support standard baud Rates in

 

 

the range 300-38400.

Parity*

Specify parity

Even, Odd, None, Mark, Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used

Optomux

 

 

 

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Poll Delay*

Time between internal polls

0-32000 seconds

 

 

default 1 second

Example

 

 

//Client Side Connections

Connections

Port, Baud, Parity, Protocol, Handshaking, Poll_Delay

R1, 9600, None, Opto22 , None

, 0.100s

4.3 Client Side Nodes

Section Title

 

 

Nodes

 

 

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric

 

 

characters

Node_ID

OPTO22 device address.

0-255

Protocol

Specify protocol used

Optomux

Port

Specify which port the device is

R1-R2, (P1-P8 with a

 

connected to the FieldServer

converter)

Example

//Client Side Nodes

Nodes

Node_Name, Node_ID, Protocol, Port

Optomux1 , 1 , Optomux , R1