Page 26 of | Page 26 of 29 |
Appendix C.2. Scaling
Scaling was added in version 1.02a and is not supported for earlier versions.
Scaling is applied by the driver when bytes and registers are stored.
When bit data is transferred in bit format than scaling is not applied. When bit data is transferred using bye format’s then scaling may be applied.
Scaling is applied using the FieldServer’s standard Map Descriptor parameters.
Data_Array_Low_Scale,
Data_Array_High_Scale,
Device_Low_Scale,
Device_High_Scale
Appendix C.3. Server Response NAK, Major and Minor Error Codes
From version 1.02c the when the Server responds with a MailBox Nak it now allocates different Major and Minor error codes to differentiate the NAK reasons.
0x05 0xbe | No Such Node | The request Node is not known by the Server. |
0x05 0xbd | No Data | The Data age is greater than the CACHE_AGE setting. |
0x05 0xbc | Other Problems | Eg. No Server MD’s defined for requested data. |
Major Error Status Codes
Error Status | Description |
| ||
01h | Illegal Service Request: | Either not defined or not supported. |
| |
02h | Insufficient Privilege: | Minor status field contains the privilege level required | ||
for the service request |
| |||
|
|
| ||
04h | Protocol Sequence Error: | The CPU has received a message that is out of order. | ||
05h | Service Request Error: | Minor status field contains the request | specific error | |
code. See table of Minor Error Status Codes below. | ||||
|
| |||
06h | Illegal Mailbox Type: | Service request mailbox type is either | undefined or | |
unexpected. |
| |||
|
|
| ||
07h | The PLC CPU's Service Request | It is recommended that the master wait a minimum of | ||
Queue is full. The master should retry | 10 ms before sending another service |
| ||
later. |
|
|
Minor Error Status Codes
Decimal | Hex | Description |
0FF | Service request has been aborted. | |
0FE | No privilege for attempted operation. | |
0FD | Unable to perform auto configuration. | |
0FC | I/O configuration is invalid. | |
0FB | Cannot clear I/O configuration. | |
0FA | Cannot replace I/O module. | |
0F9 | Task address out of range. | |
0F8 | Invalid task name referenced. | |
0F7 | Required to log in to a task for service. |