FieldServer FS-8700-66 instruction manual Appendix A. Troubleshooting Tips

Models: FS-8700-66

1 29
Download 29 pages 60.45 Kb
Page 19
Image 19
Appendix A. Troubleshooting Tips

Page 19 of 29FS-8700-66_GE-SNP Manual

Page 19 of 29

Appendix A. Troubleshooting Tips

Every 2nd message Times Out A possible cause is that the poll frequency is so low that the time between polls is greater than the Max Link Idle Time (of the PLC). If the time is exceeded the connection is closed. Thus when the next poll is received by the PLC it ignores it and hence it times out in the FieldServer. After timing out, the driver re-establishes the connection for the next poll.

Very slow Comms Rate A timer known as the T1 timer is the minimum time that must pass before a response to a message can be sent. Both ends of a SNP connection have their own T1 timer (hard coded in the driver). When a connection is made the timers are exchanged and the larger of the two is used. The drivers T1 timer is set to a very small number. SNP message #6 indicates the size of the T1 timer. You may need to configure the PLC to improve communications.

Multidrop RS-485 networks. SNP protocol specifies that their may only be one master on a network at a time. When using nameless Nodes (Node_id=0) there may be one and only one PLC on the connection.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 19
Image 19
FieldServer FS-8700-66 instruction manual Appendix A. Troubleshooting Tips